Equipment Type | Size Category (Input) | Subcategory or Rating Condition | Minimum Efficiency | Test Procedurea |
PTAC (cooling mode) Standard size | < 7,000 Btu/h | 95°F db/75°F wb outdoor airc | 11.9 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h | 14.0 - (0.300 × Cap/1000) EERd |
> 15,000 Btu/h | 9.5 EER |
PTAC (cooling mode) Nonstandard sizea | < 7,000 Btu/h | 95°F db/75°F wb outdoor airc | 9.4 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h | 10.9 - (0.213 × Cap/1000) EERd |
> 15,000 Btu/h | 7.7 EER |
PTHP (cooling mode) Standard size | < 7,000 Btu/h | 95°F db/75°F wb outdoor airc | 11.9 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h | 14.0 - (0.300 × Cap/1000) EERd |
> 15,000 Btu/h | 9.5 EER |
PTHP (cooling mode) Nonstandard sizeb | < 7,000 Btu/h | 95°F db/75°F wb outdoor airc | 9.3 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h | 10.8 - (0.213 × Cap/1000) EERd |
> 15,000 Btu/h | 7.6 EER |
PTHP (heating mode) Standard size | < 7,000 Btu/h | 47°F db/43°F wb outdoor air | 3.3 COPH | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h | 3.7 - (0.052 × Cap/1000) COPHd |
> 15,000 Btu/h | 2.90 COPH |
PTHP (heating mode) Nonstandard sizeb | < 7,000 Btu/h | 47°F db/43°F wb outdoor air | 2.7 COPH | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h | 2.9 - (0.026 × Cap/1000) COPHd |
> 15,000 Btu/h | 2.5 COPH |
SPVAC (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor airc | 11.0 EER | AHRI 390 |
≥ 65,000 Btu/h and < 135,000 Btu/h | 10.0 EER |
≥ 135,000 Btu/h and < 240,000 Btu/h | 10.0 EER |
SPVHP (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor airc | 11.0 EER | AHRI 390 |
≥ 65,000 Btu/h and < 135,000 Btu/h | 10.0 EER |
≥ 135,000 Btu/h and < 240,000 Btu/h | 10.0 EER |
SPVHP (heating mode) | <65,000 Btu/h | 47°F db/43°F wb outdoor air | 3.3 COP | AHRI 390 |
≥ 65,000 Btu/h and < 135,000 Btu/h | 3.0 COP |
≥ 135,000 Btu/h and < 240,000 Btu/h | 3.0 COP |
Room air conditioners without reverse cycle with louvered sides for applications outside U.S. | < 6,000 Btu/h | - | 11.0 CEER | ANSI/AHAMRAC-1 |
≥ 6,000 Btu/h and < 8,000 Btu/h | - | 11.0 CEER |
≥ 8,000 Btu/h and < 14,000 Btu/h | - | 10.9 CEER |
≥ 14,000 Btu/h and < 20,000 Btu/h | - | 10.7 CEER |
≥ 20,000 Btu/h and < 28,000 Btu/h | - | 9.4 CEER |
≥ 28,000 Btu/h | - | 9.0 CEER |
Room air conditioners without louvered sides | < 6,000 Btu/h | - | 10.0 CEER | ANSI/AHAMRAC-1 |
≥ 6,000 Btu/h and < 8,000 Btu/h | - | 10.0 CEER |
≥ 8,000 Btu/h and < 11,000 Btu/h | - | 9.6 CEER |
≥ 11,000 Btu/h and < 14,000 Btu/h | - | 9.5 CEER |
≥ 14,000 Btu/h and < 20,000 Btu/h | - | 9.3 CEER |
≥ 20,000 Btu/h | - | 9.4 CEER |
Room air conditioners with reverse cycle, with louvered sides for applications outside U.S. | < 20,000 Btu/h | - | 9.8 CEER | ANSI/AHAMRAC-1 |
≥ 20,000 Btu/h | - | 9.3 CEER |
Room air conditioners with reverse cycle without louvered sides for applications outside U.S. | < 14,000 Btu/h | - | 9.3 CEER | ANSI/AHAMRAC-1 |
≥ 14,000 Btu/h | - | 8.7 CEER |
Room air conditioners, casement only for applications outside U.S. | All capacities | - | 9.5 CEER | ANSI/AHAMRAC-1 |
Room air conditioners, casement-slider for application outside U.S. | All capacities | - | 10.4 CEER | ANSI/AHAMRAC-1 |