Note: | This appendix is identical to 29 C.F.R. 1910.269 Appendix B, Working on Exposed Energized Parts. However, all references to live-line barehand work have been deleted since it is prohibited in Washington state. |
I. Introduction
Electric utilities design electric power generation, transmission, and distribution installations to meet National Electrical Safety Code (NESC), ANSI C2, requirements. Electric utilities also design transmission and distribution lines to limit line outages as required by system reliability criteria1 and to withstand the maximum overvoltage's impressed on the system. Conditions such as switching surges, faults, and lightning can cause overvoltages. Electric utilities generally select insulator design and lengths and the clearances to structural parts so as to prevent outages from contaminated line insulation and during storms. Line insulator lengths and structural clearances have, over the years, come closer to the minimum approach distances used by workers. As minimum approach distances and structural clearances converge, it is increasingly important that system designers and system operating and maintenance personnel understand the concepts underlying minimum approach distances.
The information in this appendix will assist employers in complying with the minimum approach-distance requirements contained in § 1910.269(l)(3). Employers must use the technical criteria and methodology presented in this appendix in establishing minimum approach distances in accordance with § 1910.269(l)(3)(i) and Table R-3 and Table R-8. This appendix provides essential background information and technical criteria for the calculation of the required minimum approach distances for live-line work on electric power generation, transmission, and distribution installations.
Unless an employer is using the maximum transient overvoltage's specified in Table R-9 for voltages over 72.5 kilovolts, the employer must use persons knowledgeable in the techniques discussed in this appendix, and competent in the field of electric transmission and distribution system design, to determine the maximum transient overvoltage.
II. General
A. Definitions. The following definitions from § 1910.269(x) relate to work on or near electric power generation, transmission, and distribution lines and equipment and the electrical hazards they present.
Exposed. . . . Not isolated or guarded.
Guarded. Covered, fenced, enclosed, or otherwise protected, by means of suitable covers or casings, barrier rails or screens, mats, or platforms, designed to minimize the possibility, under normal conditions, of dangerous approach or inadvertent contact by persons or objects.
Note to the definition of guarded: Wires that are insulated, but not otherwise protected, are not guarded.
Insulated. Separated from other conducting surfaces by a dielectric (including air space) offering a high resistance to the passage of current.
Note to the definition of insulated: When any object is said to be insulated, it is understood to be insulated for the conditions to which it normally is subjected. Otherwise, it is, for the purpose of this section, uninsulated.
Isolated. Not readily accessible to persons unless special means for access are used.
Statistical sparkover voltage. A transient overvoltage level that produces a 97.72-percent probability of sparkover (that is, two standard deviations above the voltage at which there is a 50-percent probability of sparkover).
Statistical withstand voltage. A transient overvoltage level that produces a 0.14-percent probability of sparkover (that is, three standard deviations below the voltage at which there is a 50-percent probability of sparkover).
B. Installations energized at 50 to 300 volts. The hazards posed by installations energized at 50 to 300 volts are the same as those found in many other workplaces. That is not to say that there is no hazard, but the complexity of electrical protection required does not compare to that required for high voltage systems. The employee must avoid contact with the exposed parts, and the protective equipment used (such as rubber insulating gloves) must provide insulation for the voltages involved.
C. Exposed energized parts over 300 volts AC. Paragraph (l)(3)(i) of § 1910.269 requires the employer to establish minimum approach distances no less than the distances computed by Table R-3 for AC systems so that employees can work safely without risk of sparkover.2
Unless the employee is using electrical protective equipment, air is the insulating medium between the employee and energized parts. The distance between the employee and an energized part must be sufficient for the air to withstand the maximum transient overvoltage that can reach the worksite under the working conditions and practices the employee is using. This distance is the minimum air insulation distance, and it is equal to the electrical component of the minimum approach distance.
Normal system design may provide or include a means (such as lightning arrestors) to control maximum anticipated transient overvoltage's, or the employer may use temporary devices (portable protective gaps) or measures (such as preventing automatic circuit breaker reclosing) to achieve the same result. Paragraph (l)(3)(ii) of § 1910.269 requires the employer to determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis or assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table R-9, which specifies the following maximums for ac systems:
72.6 to 420.0 kilovolts-3.5 per unit
420.1 to 550.0 kilovolts-3.0 per unit
550.1 to 800.0 kilovolts-2.5 per unit
See paragraph IV.A.2, later in this appendix, for additional discussion of maximum transient overvoltages.
D. Types of exposures. Employees working on or near energized electric power generation, transmission, and distribution systems face two kinds of exposures: Phase-to-ground and phase-to-phase. The exposure is phase-to-ground with respect to an energized part, when the employee is at ground potential.
III. Determination of Minimum Approach Distances for AC Voltages Greater Than 300 Volts
A. Voltages of 301 to 5,000 volts. Test data generally forms the basis of minimum air insulation distances. The lowest voltage for which sufficient test data exists is 5,000 volts, and these data indicate that the minimum air insulation distance at that voltage is 20 millimeters (1 inch). Because the minimum air insulation distance increases with increasing voltage, and, conversely, decreases with decreasing voltage, an assumed minimum air insulation distance of 20 millimeters will protect against sparkover at voltages of 301 to 5,000 volts. Thus, 20 millimeters is the electrical component of the minimum approach distance for these voltages.
B. Voltages of 5.1 to 72.5 kilovolts. For voltages from 5.1 to 72.5 kilovolts, the Occupational Safety and Health Administration bases the methodology for calculating the electrical component of the minimum approach distance on Institute of Electrical and Electronic Engineers (IEEE) Standard 4-1995, Standard Techniques for High-Voltage Testing. Table 1 lists the critical sparkover distances from that standard as listed in IEEE Std 516-2009, IEEE Guide for Maintenance Methods on Energized Power Lines.
Table 1
Sparkover Distance for Rod-to-rod Gap
60 Hz Rod-to-Rod sparkover (kV peak) | Gap spacing from IEEE Std 4-1995 (cm) |
25 . . . . | 2 |
36 . . . . | 3 |
46 . . . . | 4 |
53 . . . . | 5 |
60 . . . . | 6 |
70 . . . . | 8 |
79 . . . . | 10 |
86 . . . . | 12 |
95 . . . . | 14 |
104 . . . . | 16 |
112 . . . . | 18 |
120 . . . . | 20 |
143 . . . . | 25 |
167 . . . . | 30 |
192 . . . . | 35 |
218 . . . . | 40 |
243 . . . . | 45 |
270 . . . . | 50 |
322 . . . . | 60 |
Source: IEEE Std 516-2009.
To use this table to determine the electrical component of the minimum approach distance, the employer must determine the peak phase-to-ground transient overvoltage and select a gap from the table that corresponds to that voltage as a withstand voltage rather than a critical sparkover voltage. To calculate the electrical component of the minimum approach distance for voltages between 5 and 72.5 kilovolts, use the following procedure:
1. Divide the phase-to-phase voltage by the square root of 3 to convert it to a phase-to-ground voltage.
2. Multiply the phase-to-ground voltage by the square root of 2 to convert the rms value of the voltage to the peak phase-to-ground voltage.
3. Multiply the peak phase-to-ground voltage by the maximum per-unit transient overvoltage, which, for this voltage range, is 3.0, as discussed later in this appendix. This is the maximum phase-to-ground transient overvoltage, which corresponds to the withstand voltage for the relevant exposure.3
4. Divide the maximum phase-to-ground transient overvoltage by 0.85 to determine the corresponding critical sparkover voltage. (The critical sparkover voltage is 3 standard deviations (or 15 percent) greater than the withstand voltage.)
5. Determine the electrical component of the minimum approach distance from Table 1 through interpolation.
Table 2 illustrates how to derive the electrical component of the minimum approach distance for voltages from 5.1 to 72.5 kilovolts, before the application of any altitude correction factor, as explained later.
Table 2
Calculating the Electrical Component Of MAD 751 V To 72.5 KV
Step | Maximum system phase-to-phase voltage (kV) |
15 | 36 | 46 | 72.5 |
1. Divide by √3 . . . . | 8.7 | 20.8 | 26.6 | 41.9 |
2. Multiply by √2 . . . . | 12.2 | 29.4 | 37.6 | 59.2 |
3. Multiply by 3.0 . . . . | 36.7 | 88.2 | 112.7 | 177.6 |
4. Divide by 0.85 . . . . | 43.2 | 103.7 | 132.6 | 208.9 |
5. Interpolate from Table 1 . . . . | 3+(7.2/10)*1 | 14+(8.7/9)*2 | 20+(12.6/23)*5 | 35+(16.9/26)*5 |
Electrical component of MAD (cm) . . . . | 3.72 | 15.93 | 22.74 | 38.25 |
C. Voltages of 72.6 to 800 kilovolts. For voltages of 72.6 kilovolts to 800 kilovolts, this section bases the electrical component of minimum approach distances, before the application of any altitude correction factor, on the following formula:
Equation 1 - For voltages of 72.6 kV to 800 kV
D = 0.3048(C + a) VL-GT
Where:
D = Electrical component of the minimum approach distance in air in meters;
C = A correction factor associated with the variation of gap sparkover with voltage;
a = A factor relating to the saturation of air at system voltages of 345 kilovolts or higher;4
VL-G = Maximum system line-to-ground rms voltage in kilovolts - It should be the "actual" maximum, or the normal highest voltage for the range (for example, 10 percent above the nominal voltage); and
T = Maximum transient overvoltage factor in per unit.
In Equation 1, C is 0.01: (1) For phase-to-ground exposures that the employer can demonstrate consist only of air across the approach distance (gap) and (2) for phase-to-phase exposures if the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap. Otherwise, C is 0.011.
In Equation 1, the term a varies depending on whether the employee's exposure is phase-to-ground or phase-to-phase and on whether objects are in the gap. The employer must use the equations in Table 3 to calculate a. Sparkover test data with insulation spanning the gap form the basis for the equations for phase-to-ground exposures, and sparkover test data with only air in the gap form the basis for the equations for phase-to-phase exposures. The phase-to-ground equations result in slightly higher values of a, and, consequently, produce larger minimum approach distances, than the phase-to-phase equations for the same value of VPeak.
Table 3
Equations for Calculating the Surge Factor, a
Phase-to-ground exposures |
VPeak = TL-GVL-G√2 . . . . | 635 kV or less 0 | 635.1 to 915 kV (VPeak- 635)/140,000 | 915.1 to 1,050 kV (VPeak-645)/135,000 |
a. . . . |
VPeak= TL-GVL-G√2 . . . . | More than 1,050 kV |
a. . . . | (VPeak-675)/125,000 |
Phase-to-phase exposures 1 |
VPeak = (1.35TL-G + 0.45)VL-G√2 . . . . | 630 kV or less 0 | 630.1 to 848 kV (VPeak-630)/155,000 | 848.1 to 1,131 kV (VPeak-633.6)/152,207 |
a. . . . |
VPeak = (1.35TL-G + 0.45)VL-G√2 . . . . | 1,131.1 to 1,485 kV (VPeak-628)/153,846 | More than 1,485 kV (VPeak-350.5)/203,666 |
a. . . . |
1Use the equations for phase-to-ground exposures (with VPeak for phase-to-phase exposures) unless the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap.
In Equation 1, T is the maximum transient overvoltage factor in per unit. As noted earlier, § 1910.269(l)(3)(ii) requires the employer to determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis or assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table R-9. For phase-to-ground exposures, the employer uses this value, called TL-G, as T in Equation 1. IEEE Std 516-2009 provides the following formula to calculate the phase-to-phase maximum transient overvoltage, TL-L, from TL-G:
TL-L = 1.35TL-G + 0.45
For phase-to-phase exposures, the employer uses this value as T in Equation 1.
D. Provisions for inadvertent movement. The minimum approach distance must include an "adder" to compensate for the inadvertent movement of the worker relative to an energized part or the movement of the part relative to the worker. This "adder" must account for this possible inadvertent movement and provide the worker with a comfortable and safe zone in which to work. Employers must add the distance for inadvertent movement (called the "ergonomic component of the minimum approach distance") to the electrical component to determine the total safe minimum approach distances used in live-line work.
The Occupational Safety and Health Administration based the ergonomic component of the minimum approach distance on response time-distance analysis. This technique uses an estimate of the total response time to a hazardous incident and converts that time to the distance traveled. For example, the driver of a car takes a given amount of time to respond to a "stimulus" and stop the vehicle. The elapsed time involved results in the car's traveling some distance before coming to a complete stop. This distance depends on the speed of the car at the time the stimulus appears and the reaction time of the driver.
In the case of live-line work, the employee must first perceive that he or she is approaching the danger zone. Then, the worker responds to the danger and must decelerate and stop all motion toward the energized part. During the time it takes to stop, the employee will travel some distance. This is the distance the employer must add to the electrical component of the minimum approach distance to obtain the total safe minimum approach distance.
At voltages from 751 volts to 72.5 kilovolts,5 the electrical component of the minimum approach distance is smaller than the ergonomic component. At 72.5 kilovolts, the electrical component is only a little more than 0.3 meters (1 foot). An ergonomic component of the minimum approach distance must provide for all the worker's unanticipated movements. At these voltages, workers generally use rubber insulating gloves; however, these gloves protect only a worker's hands and arms. Therefore, the energized object must be at a safe approach distance to protect the worker's face. In this case, 0.61 meters (2 feet) is a sufficient and practical ergonomic component of the minimum approach distance.
For voltages between 72.6 and 800 kilovolts, employees must use different work practices during energized line work. Generally, employees use live-line tools (hot sticks) to perform work on energized equipment. These tools, by design, keep the energized part at a constant distance from the employee and, thus, maintain the appropriate minimum approach distance automatically.
The location of the worker and the type of work methods the worker is using also influence the length of the ergonomic component of the minimum approach distance. In this higher voltage range, the employees use work methods that more tightly control their movements than when the workers perform work using rubber insulating gloves. The worker, therefore, is farther from the energized line or equipment and must be more precise in his or her movements just to perform the work. For these reasons, this section adopts an ergonomic component of the minimum approach distance of 0.31 m (1 foot) for voltages between 72.6 and 800 kilovolts.
Table 4 summarizes the ergonomic component of the minimum approach distance for various voltage ranges.
Table 4
Ergonomic Component of Minimum Approach Distance
Voltage range (kV) | Distance |
m | ft |
0.301 to 0.750 . . . . | 0.31 | 1.0 |
0.751 to 72.5 . . . . | 0.61 | 2.0 |
72.6 to 800 . . . . | 0.31 | 1.0 |
Note: | The employer must add this distance to the electrical component of the minimum approach distance to obtain the full minimum approach distance. |
The ergonomic component of the minimum approach distance accounts for errors in maintaining the minimum approach distance (which might occur, for example, if an employee misjudges the length of a conductive object he or she is holding), and for errors in judging the minimum approach distance. The ergonomic component also accounts for inadvertent movements by the employee, such as slipping. In contrast, the working position selected to properly maintain the minimum approach distance must account for all of an employee's reasonably likely movements and still permit the employee to adhere to the applicable minimum approach distance. (See Figure 1.) Reasonably likely movements include an employee's adjustments to tools, equipment, and working positions and all movements needed to perform the work. For example, the employee should be able to perform all of the following actions without straying into the minimum approach distance:
• Adjust his or her hardhat;
• Maneuver a tool onto an energized part with a reasonable amount of overreaching or underreaching;
• Reach for and handle tools, material, and equipment passed to him or her; and
• Adjust tools, and replace components on them, when necessary during the work procedure.
The training of qualified employees required under § 1910.269(a)(2), and the job planning and briefing required under § 1910.269(c), must address selection of a proper working position.
Figure 1 - Maintaining the Minimum Approach Distance
E. Miscellaneous correction factors. Changes in the air medium that forms the insulation influences the strength of an air gap. A brief discussion of each factor follows.
1. Dielectric strength of air. The dielectric strength of air in a uniform electric field at standard atmospheric conditions is approximately 3 kilovolts per millimeter.6
The pressure, temperature, and humidity of the air, the shape, dimensions, and separation of the electrodes, and the characteristics of the applied voltage (wave shape) affect the disruptive gradient.
2. Atmospheric effect. The empirically determined electrical strength of a given gap is normally applicable at standard atmospheric conditions (20°C, 101.3 kilopascals, 11 grams/cubic centimeter humidity). An increase in the density (humidity) of the air inhibits sparkover for a given air gap. The combination of temperature and air pressure that results in the lowest gap sparkover voltage is high temperature and low pressure. This combination of conditions is not likely to occur. Low air pressure, generally associated with high humidity, causes increased electrical strength. An average air pressure generally correlates with low humidity. Hot and dry working conditions normally result in reduced electrical strength. The equations for minimum approach distances in Table R-3 assume standard atmospheric conditions.
3. Altitude. The reduced air pressure at high altitudes causes a reduction in the electrical strength of an air gap. An employer must increase the minimum approach distance by about 3 percent per 300 meters (1,000 feet) of increased altitude for altitudes above 900 meters (3,000 feet). Table R-5 specifies the altitude correction factor that the employer must use in calculating minimum approach distances.
IV. Determining Minimum Approach Distances
A. Factors Affecting Voltage Stress at the Worksite.
1. System voltage (nominal). The nominal system voltage range determines the voltage for purposes of calculating minimum approach distances. The employer selects the range in which the nominal system voltage falls, as given in the relevant table, and uses the highest value within that range in per unit calculations.
2. Transient overvoltages. Operation of switches or circuit breakers, a fault on a line or circuit or on an adjacent circuit, and similar activities may generate transient overvoltages on an electrical system. Each overvoltage has an associated transient voltage wave shape. The wave shape arriving at the site and its magnitude vary considerably.
In developing requirements for minimum approach distances, the Occupational Safety and Health Administration considered the most common wave shapes and the magnitude of transient overvoltages found on electric power generation, transmission, and distribution systems. The equations in Table R-3 for minimum approach distances use per-unit maximum transient overvoltages, which are relative to the nominal maximum voltage of the system. For example, a maximum transient overvoltage value of 3.0 per unit indicates that the highest transient overvoltage is 3.0 times the nominal maximum system voltage.
3. Typical magnitude of overvoltages. Table 5 lists the magnitude of typical transient overvoltages.
Table 5
Magnitude of Typical Transient Overvoltages
Cause | Magnitude (per unit) |
Energized 200-mile line without closing resistors . . . . | 3.5 |
Energized 200-mile line with one-step closing resistor . . . . | 2.1 |
Energized 200-mile line with multistep resistor . . . . | 2.5 |
Reclosing with trapped charge one-step resistor . . . . | 2.2 |
Opening surge with single restrike . . . . | 3.0 |
Fault initiation unfaulted phase . . . . | 2.1 |
Fault initiation adjacent circuit . . . . | 2.5 |
Fault clearing . . . . | 1.7 to 1.9 |
4. Standard deviation-air-gap withstand. For each air gap length under the same atmospheric conditions, there is a statistical variation in the breakdown voltage. The probability of breakdown against voltage has a normal (Gaussian) distribution. The standard deviation of this distribution varies with the wave shape, gap geometry, and atmospheric conditions. The withstand voltage of the air gap is three standard deviations (3s) below the critical sparkover voltage. (The critical sparkover voltage is the crest value of the impulse wave that, under specified conditions, causes sparkover 50 percent of the time. An impulse wave of three standard deviations below this value, that is, the withstand voltage, has a probability of sparkover of approximately 1 in 1,000.)
5. Broken Insulators. Tests show reductions in the insulation strength of insulator strings with broken skirts. Broken units may lose up to 70 percent of their withstand capacity. Because an employer cannot determine the insulating capability of a broken unit without testing it, the employer must consider damaged units in an insulator to have no insulating value. Additionally, the presence of a live-line tool alongside an insulator string with broken units may further reduce the overall insulating strength. The number of good units that must be present in a string for it to be "insulated" as defined by § 1910.269(x) depends on the maximum overvoltage possible at the worksite.
B. Minimum Approach Distances Based on Known, Maximum-Anticipated Per-Unit Transient Overvoltages.
1. Determining the minimum approach distance for AC systems. Under § 1910.269(l)(3)(ii), the employer must determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis or must assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table R-9. When the employer conducts an engineering analysis of the system and determines that the maximum transient overvoltage is lower than specified by Table R-9, the employer must ensure that any conditions assumed in the analysis, for example, that employees block reclosing on a circuit or install portable protective gaps, are present during energized work. To ensure that these conditions are present, the employer may need to institute new livework procedures reflecting the conditions and limitations set by the engineering analysis.
2. Calculation of reduced approach distance values. An employer may take the following steps to reduce minimum approach distances when the maximum transient overvoltage on the system (that is, the maximum transient overvoltage without additional steps to control overvoltages) produces unacceptably large minimum approach distances:
Step 1. Determine the maximum voltage (with respect to a given nominal voltage range) for the energized part.
Step 2. Determine the technique to use to control the maximum transient overvoltage. (See paragraphs IV.C and IV.D of this appendix.) Determine the maximum transient overvoltage that can exist at the worksite with that form of control in place and with a confidence level of 3s. This voltage is the withstand voltage for the purpose of calculating the appropriate minimum approach distance.
Step 3. Direct employees to implement procedures to ensure that the control technique is in effect during the course of the work.
Step 4. Using the new value of transient overvoltage in per unit, calculate the required minimum approach distance from Table R-3.
C. Methods of Controlling Possible Transient Overvoltage Stress Found on a System.
1. Introduction. There are several means of controlling overvoltages that occur on transmission systems. For example, the employer can modify the operation of circuit breakers or other switching devices to reduce switching transient overvoltages. Alternatively, the employer can hold the overvoltage to an acceptable level by installing surge arresters or portable protective gaps on the system. In addition, the employer can change the transmission system to minimize the effect of switching operations. Section 4.8 of IEEE Std 516-2009 describes various ways of controlling, and thereby reducing, maximum transient overvoltages.
2. Operation of circuit breakers.7 The maximum transient overvoltage that can reach the worksite is often the result of switching on the line on which employees are working. Disabling automatic reclosing during energized line work, so that the line will not be reenergized after being opened for any reason, limits the maximum switching surge overvoltage to the larger of the opening surge or the greatest possible fault-generated surge, provided that the devices (for example, insertion resistors) are operable and will function to limit the transient overvoltage and that circuit breaker restrikes do not occur. The employer must ensure the proper functioning of insertion resistors and other overvoltage-limiting devices when the employer's engineering analysis assumes their proper operation to limit the overvoltage level. If the employer cannot disable the reclosing feature (because of system operating conditions), other methods of controlling the switching surge level may be necessary.
Transient surges on an adjacent line, particularly for double circuit construction, may cause a significant overvoltage on the line on which employees are working. The employer's engineering analysis must account for coupling to adjacent lines.
3. Surge arresters. The use of modern surge arresters allows a reduction in the basic impulse-insulation levels of much transmission system equipment. The primary function of early arresters was to protect the system insulation from the effects of lightning. Modern arresters not only dissipate lightning-caused transients, but may also control many other system transients caused by switching or faults.
The employer may use properly designed arresters to control transient overvoltages along a transmission line and thereby reduce the requisite length of the insulator string and possibly the maximum transient overvoltage on the line.8
4. Switching restrictions. Another form of overvoltage control involves establishing switching restrictions, whereby the employer prohibits the operation of circuit breakers until certain system conditions are present. The employer restricts switching by using a tagging system, similar to that used for a permit, except that the common term used for this activity is a "hold-off" or "restriction." These terms indicate that the restriction does not prevent operation, but only modifies the operation during the livework activity.
D. Minimum Approach Distance Based on Control of Maximum Transient Overvoltage at the Worksite.
When the employer institutes control of maximum transient overvoltage at the worksite by installing portable protective gaps, the employer may calculate the minimum approach distance as follows:
Step 1. Select the appropriate withstand voltage for the protective gap based on system requirements and an acceptable probability of gap sparkover.9
Step 2. Determine a gap distance that provides a withstand voltage10 greater than or equal to the one selected in the first step.11
Step 3. Use 110 percent of the gap's critical sparkover voltage to determine the phase-to-ground peak voltage at gap sparkover (VPPG Peak).
Step 4. Determine the maximum transient overvoltage, phase-to-ground, at the worksite from the following formula:
Step 5. Use this value of T12 in the equation in Table R-3 to obtain the minimum approach distance. If the worksite is no more than 900 meters (3,000 feet) above sea level, the employer may use this value of T to determine the minimum approach distance from Table 14 through Table 21.
Note: | All rounding must be to the next higher value (that is, always round up). |
Sample protective gap calculations.
Problem: Employees are to perform work on a 500-kilovolt transmission line at sea level that is subject to transient overvoltages of 2.4 p.u. The maximum operating voltage of the line is 550 kilovolts. Determine the length of the protective gap that will provide the minimum practical safe approach distance. Also, determine what that minimum approach distance is:
Step 1. Calculate the smallest practical maximum transient overvoltage (1.25 times the crest phase-to-ground voltage):13
This value equals the withstand voltage of the protective gap.
Step 2. Using test data for a particular protective gap, select a gap that has a critical sparkover voltage greater than or equal to:
561kV ÷ 0.85 = 660kV
For example, if a protective gap with a 1.22-m (4.0-foot) spacing tested to a critical sparkover voltage of 665 kilovolts (crest), select this gap spacing.
Step 3. The phase-to-ground peak voltage at gap sparkover (VPPG Peak) is 110 percent of the value from the previous step:
665kV × 1.10 = 732kV
This value corresponds to the withstand voltage of the electrical component of the minimum approach distance.
Step 4. Use this voltage to determine the worksite value of T:
Step 5. Use this value of T in the equation in Table R-3 to obtain the minimum approach distance, or look up the minimum approach distance in Table 14 through Table 21:
MAD = 2.29 m (7.6 ft).
E. Location of Protective Gaps.
1. Adjacent structures. The employer may install the protective gap on a structure adjacent to the worksite, as this practice does not significantly reduce the protection afforded by the gap.
2. Terminal stations. Gaps installed at terminal stations of lines or circuits provide a level of protection; however, that level of protection may not extend throughout the length of the line to the worksite. The use of substation terminal gaps raises the possibility that separate surges could enter the line at opposite ends, each with low enough magnitude to pass the terminal gaps without sparkover. When voltage surges occur simultaneously at each end of a line and travel toward each other, the total voltage on the line at the point where they meet is the arithmetic sum of the two surges. A gap installed within 0.8 km (0.5 mile) of the worksite will protect against such intersecting waves. Engineering studies of a particular line or system may indicate that employers can adequately protect employees by installing gaps at even more distant locations. In any event, unless using the default values for T from Table R-9, the employer must determine T at the worksite.
3. Worksite. If the employer installs protective gaps at the worksite, the gap setting establishes the worksite impulse insulation strength. Lightning strikes as far as 6 miles from the worksite can cause a voltage surge greater than the gap withstand voltage, and a gap sparkover can occur. In addition, the gap can sparkover from overvoltages on the line that exceed the withstand voltage of the gap. Consequently, the employer must protect employees from hazards resulting from any sparkover that could occur.
F. Disabling automatic reclosing. There are two reasons to disable the automatic-reclosing feature of circuit-interrupting devices while employees are performing live-line work:
• To prevent reenergization of a circuit faulted during the work, which could create a hazard or result in more serious injuries or damage than the injuries or damage produced by the original fault;
• To prevent any transient overvoltage caused by the switching surge that would result if the circuit were reenergized.
However, due to system stability considerations, it may not always be feasible to disable the automatic-reclosing feature.
V. Minimum Approach-Distance Tables
Note: | Tables 6 through 13 have been deleted. They became obsolete on April 1, 2015. Employers may use the minimum approach distances in Table 14 through Table 21 provided that the employer follows the notes to those tables. |
B. Alternative minimum approach distances. Employers may use the minimum approach distances in Table 14 through Table 21 provided that the employer follows the notes to those tables.
Table 14
AC Minimum Approach Distances-72.6 to 121.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 0.67 | 2.2 | 0.84 | 2.8 |
1.6 . . . . | 0.69 | 2.3 | 0.87 | 2.9 |
1.7 . . . . | 0.71 | 2.3 | 0.90 | 3.0 |
1.8 . . . . | 0.74 | 2.4 | 0.93 | 3.1 |
1.9 . . . . | 0.76 | 2.5 | 0.96 | 3.1 |
2.0 . . . . | 0.78 | 2.6 | 0.99 | 3.2 |
2.1 . . . . | 0.81 | 2.7 | 1.01 | 3.3 |
2.2 . . . . | 0.83 | 2.7 | 1.04 | 3.4 |
2.3 . . . . | 0.85 | 2.8 | 1.07 | 3.5 |
2.4 . . . . | 0.88 | 2.9 | 1.10 | 3.6 |
2.5 . . . . | 0.90 | 3.0 | 1.13 | 3.7 |
2.6 . . . . | 0.92 | 3.0 | 1.16 | 3.8 |
2.7 . . . . | 0.95 | 3.1 | 1.19 | 3.9 |
2.8 . . . . | 0.97 | 3.2 | 1.22 | 4.0 |
2.9 . . . . | 0.99 | 3.2 | 1.24 | 4.1 |
3.0 . . . . | 1.02 | 3.3 | 1.27 | 4.2 |
3.1 . . . . | 1.04 | 3.4 | 1.30 | 4.3 |
3.2 . . . . | 1.06 | 3.5 | 1.33 | 4.4 |
3.3 . . . . | 1.09 | 3.6 | 1.36 | 4.5 |
3.4 . . . . | 1.11 | 3.6 | 1.39 | 4.6 |
3.5 . . . . | 1.13 | 3.7 | 1.42 | 4.7 |
Table 15
AC Minimum Approach Distances-121.1 to 145.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 0.74 | 2.4 | 0.95 | 3.1 |
1.6 . . . . | 0.76 | 2.5 | 0.98 | 3.2 |
1.7 . . . . | 0.79 | 2.6 | 1.02 | 3.3 |
1.8 . . . . | 0.82 | 2.7 | 1.05 | 3.4 |
1.9 . . . . | 0.85 | 2.8 | 1.08 | 3.5 |
2.0 . . . . | 0.88 | 2.9 | 1.12 | 3.7 |
2.1 . . . . | 0.90 | 3.0 | 1.15 | 3.8 |
2.2 . . . . | 0.93 | 3.1 | 1.19 | 3.9 |
2.3 . . . . | 0.96 | 3.1 | 1.22 | 4.0 |
2.4 . . . . | 0.99 | 3.2 | 1.26 | 4.1 |
2.5 . . . . | 1.02 | 3.3 | 1.29 | 4.2 |
2.6 . . . . | 1.04 | 3.4 | 1.33 | 4.4 |
2.7 . . . . | 1.07 | 3.5 | 1.36 | 4.5 |
2.8 . . . . | 1.10 | 3.6 | 1.39 | 4.6 |
2.9 . . . . | 1.13 | 3.7 | 1.43 | 4.7 |
3.0 . . . . | 1.16 | 3.8 | 1.46 | 4.8 |
3.1 . . . . | 1.19 | 3.9 | 1.50 | 4.9 |
3.2 . . . . | 1.21 | 4.0 | 1.53 | 5.0 |
3.3 . . . . | 1.24 | 4.1 | 1.57 | 5.2 |
3.4 . . . . | 1.27 | 4.2 | 1.60 | 5.2 |
3.5 . . . . | 1.30 | 4.3 | 1.64 | 5.4 |
Table 16
AC Minimum Approach Distances-145.1 to 169.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 0.81 | 2.7 | 1.05 | 3.4 |
1.6 . . . . | 0.84 | 2.8 | 1.09 | 3.6 |
1.7 . . . . | 0.87 | 2.9 | 1.13 | 3.7 |
1.8 . . . . | 0.90 | 3.0 | 1.17 | 3.8 |
1.9 . . . . | 0.94 | 3.1 | 1.21 | 4.0 |
2.0 . . . . | 0.97 | 3.2 | 1.25 | 4.1 |
2.1 . . . . | 1.00 | 3.3 | 1.29 | 4.2 |
2.2 . . . . | 1.03 | 3.4 | 1.33 | 4.4 |
2.3 . . . . | 1.07 | 3.5 | 1.37 | 4.5 |
2.4 . . . . | 1.10 | 3.6 | 1.41 | 4.6 |
2.5 . . . . | 1.13 | 3.7 | 1.45 | 4.8 |
2.6 . . . . | 1.17 | 3.8 | 1.49 | 4.9 |
2.7 . . . . | 1.20 | 3.9 | 1.53 | 5.0 |
2.8 . . . . | 1.23 | 4.0 | 1.57 | 5.2 |
2.9 . . . . | 1.26 | 4.1 | 1.61 | 5.3 |
3.0 . . . . | 1.30 | 4.3 | 1.65 | 5.4 |
3.1 . . . . | 1.33 | 4.4 | 1.70 | 5.6 |
3.2 . . . . | 1.36 | 4.5 | 1.76 | 5.8 |
3.3 . . . . | 1.39 | 4.6 | 1.82 | 6.0 |
3.4 . . . . | 1.43 | 4.7 | 1.88 | 6.2 |
3.5 . . . . | 1.46 | 4.8 | 1.94 | 6.4 |
Table 17
AC Minimum Approach Distances-169.1 to 242.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 1.02 | 3.3 | 1.37 | 4.5 |
1.6 . . . . | 1.06 | 3.5 | 1.43 | 4.7 |
1.7 . . . . | 1.11 | 3.6 | 1.48 | 4.9 |
1.8 . . . . | 1.16 | 3.8 | 1.54 | 5.1 |
1.9 . . . . | 1.21 | 4.0 | 1.60 | 5.2 |
2.0 . . . . | 1.25 | 4.1 | 1.66 | 5.4 |
2.1 . . . . | 1.30 | 4.3 | 1.73 | 5.7 |
2.2 . . . . | 1.35 | 4.4 | 1.81 | 5.9 |
2.3 . . . . | 1.39 | 4.6 | 1.90 | 6.2 |
2.4 . . . . | 1.44 | 4.7 | 1.99 | 6.5 |
2.5 . . . . | 1.49 | 4.9 | 2.08 | 6.8 |
2.6 . . . . | 1.53 | 5.0 | 2.17 | 7.1 |
2.7 . . . . | 1.58 | 5.2 | 2.26 | 7.4 |
2.8 . . . . | 1.63 | 5.3 | 2.36 | 7.7 |
2.9 . . . . | 1.67 | 5.5 | 2.45 | 8.0 |
3.0 . . . . | 1.72 | 5.6 | 2.55 | 8.4 |
3.1 . . . . | 1.77 | 5.8 | 2.65 | 8.7 |
3.2 . . . . | 1.81 | 5.9 | 2.76 | 9.1 |
3.3 . . . . | 1.88 | 6.2 | 2.86 | 9.4 |
3.4 . . . . | 1.95 | 6.4 | 2.97 | 9.7 |
3.5 . . . . | 2.01 | 6.6 | 3.08 | 10.1 |
Table 18
AC Minimum Approach Distances-242.1 to 362.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 1.37 | 4.5 | 1.99 | 6.5 |
1.6 . . . . | 1.44 | 4.7 | 2.13 | 7.0 |
1.7 . . . . | 1.51 | 5.0 | 2.27 | 7.4 |
1.8 . . . . | 1.58 | 5.2 | 2.41 | 7.9 |
1.9 . . . . | 1.65 | 5.4 | 2.56 | 8.4 |
2.0 . . . . | 1.72 | 5.6 | 2.71 | 8.9 |
2.1 . . . . | 1.79 | 6.1 | 2.87 | 9.4 |
2.2 . . . . | 1.87 | 6.1 | 3.03 | 9.9 |
2.3 . . . . | 1.97 | 6.5 | 3.20 | 10.5 |
2.4 . . . . | 2.08 | 6.8 | 3.37 | 11.1 |
2.5 . . . . | 2.19 | 7.2 | 3.55 | 11.6 |
2.6 . . . . | 2.29 | 7.5 | 3.73 | 12.2 |
2.7 . . . . | 2.41 | 7.9 | 3.91 | 12.8 |
2.8 . . . . | 2.52 | 8.3 | 4.10 | 13.5 |
2.9 . . . . | 2.64 | 8.7 | 4.29 | 14.1 |
3.0 . . . . | 2.76 | 9.1 | 4.49 | 14.7 |
3.1 . . . . | 2.88 | 9.4 | 4.69 | 15.4 |
3.2 . . . . | 3.01 | 9.9 | 4.90 | 16.1 |
3.3 . . . . | 3.14 | 10.3 | 5.11 | 16.8 |
3.4 . . . . | 3.27 | 10.7 | 5.32 | 17.5 |
3.5 . . . . | 3.41 | 11.2 | 5.52 | 18.1 |
Table 19
AC Minimum Approach Distances-362.1 to 420.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 1.53 | 5.0 | 2.40 | 7.9 |
1.6 . . . . | 1.62 | 5.3 | 2.58 | 8.5 |
1.7 . . . . | 1.70 | 5.6 | 2.75 | 9.0 |
1.8 . . . . | 1.78 | 5.8 | 2.94 | 9.6 |
1.9 . . . . | 1.88 | 6.2 | 3.13 | 10.3 |
2.0 . . . . | 1.99 | 6.5 | 3.33 | 10.9 |
2.1 . . . . | 2.12 | 7.0 | 3.53 | 11.6 |
2.2 . . . . | 2.24 | 7.3 | 3.74 | 12.3 |
2.3 . . . . | 2.37 | 7.8 | 3.95 | 13.0 |
2.4 . . . . | 2.50 | 8.2 | 4.17 | 13.7 |
2.5 . . . . | 2.64 | 8.7 | 4.40 | 14.4 |
2.6 . . . . | 2.78 | 9.1 | 4.63 | 15.2 |
2.7 . . . . | 2.93 | 9.6 | 4.87 | 16.0 |
2.8 . . . . | 3.07 | 10.1 | 5.11 | 16.8 |
2.9 . . . . | 3.23 | 10.6 | 5.36 | 17.6 |
3.0 . . . . | 3.38 | 11.1 | 5.59 | 18.3 |
3.1 . . . . | 3.55 | 11.6 | 5.82 | 19.1 |
3.2 . . . . | 3.72 | 12.2 | 6.07 | 19.9 |
3.3 . . . . | 3.89 | 12.8 | 6.31 | 20.7 |
3.4 . . . . | 4.07 | 13.4 | 6.56 | 21.5 |
3.5 . . . . | 4.25 | 13.9 | 6.81 | 22.3 |
Table 20
AC Minimum Approach Distances-420.1 to 550.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 1.95 | 6.4 | 3.46 | 11.4 |
1.6 . . . . | 2.11 | 6.9 | 3.73 | 12.2 |
1.7 . . . . | 2.28 | 7.5 | 4.02 | 13.2 |
1.8 . . . . | 2.45 | 8.0 | 4.31 | 14.1 |
1.9 . . . . | 2.62 | 8.6 | 4.61 | 15.1 |
2.0 . . . . | 2.81 | 9.2 | 4.92 | 16.1 |
2.1 . . . . | 3.00 | 9.8 | 5.25 | 17.2 |
2.2 . . . . | 3.20 | 10.5 | 5.55 | 18.2 |
2.3 . . . . | 3.40 | 11.2 | 5.86 | 19.2 |
2.4 . . . . | 3.62 | 11.9 | 6.18 | 20.3 |
2.5 . . . . | 3.84 | 12.6 | 6.50 | 21.3 |
2.6 . . . . | 4.07 | 13.4 | 6.83 | 22.4 |
2.7 . . . . | 4.31 | 14.1 | 7.18 | 23.6 |
2.8 . . . . | 4.56 | 15.0 | 7.52 | 24.7 |
2.9 . . . . | 4.81 | 15.8 | 7.88 | 25.9 |
3.0 . . . . | 5.07 | 16.6 | 8.24 | 27.0 |
Table 21
AC Minimum Approach Distances-550.1 to 800.0 KV
T (p.u.) | Phase-to-ground exposure | Phase-to-phase exposure |
m | ft | m | ft |
1.5 . . . . | 3.16 | 10.4 | 5.97 | 19.6 |
1.6 . . . . | 3.46 | 11.4 | 6.43 | 21.1 |
1.7 . . . . | 3.78 | 12.4 | 6.92 | 22.7 |
1.8 . . . . | 4.12 | 13.5 | 7.42 | 24.3 |
1.9 . . . . | 4.47 | 14.7 | 7.93 | 26.0 |
2.0 . . . . | 4.83 | 15.8 | 8.47 | 27.8 |
2.1 . . . . | 5.21 | 17.1 | 9.02 | 29.6 |
2.2 . . . . | 5.61 | 18.4 | 9.58 | 31.4 |
2.3 . . . . | 6.02 | 19.8 | 10.16 | 33.3 |
2.4 . . . . | 6.44 | 21.1 | 10.76 | 35.3 |
2.5 . . . . | 6.88 | 22.6 | 11.38 | 37.3 |
Notes to Table 14 through Table 21: |
| 1. The employer must determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis, as required by § 1910.269(l)(3)(ii), or assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table R-9. |
| 2. For phase-to-phase exposures, the employer must demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap. |
| The worksite must be at an elevation of 900 meters (3,000 feet) or less above sea level. |
| 1Federal, state, and local regulatory bodies and electric utilities set reliability requirements that limit the number and duration of system outages. |
| 2Sparkover is a disruptive electric discharge in which an electric arc forms and electric current passes through air. |
| 3The withstand voltage is the voltage at which sparkover is not likely to occur across a specified distance. It is the voltage taken at the 3s point below the sparkover voltage, assuming that the sparkover curve follows a normal distribution. |
| 4Test data demonstrates that the saturation factor is greater than 0 at peak voltages of about 630 kilovolts. Systems operating at 345 kilovolts (or maximum system voltages of 362 kilovolts) can have peak maximum transient overvoltages exceeding 630 kilovolts. Table R-3 sets equations for calculating a based on peak voltage. |
| 5For voltages of 50 to 300 volts, Table R-3 specifies a minimum approach distance of "avoid contact." The minimum approach distance for this voltage range contains neither an electrical component nor an ergonomic component. |
| 6For the purposes of estimating arc length, § 1910.269 generally assumes a more conservative dielectric strength of 10 kilovolts per 25.4 millimeters, consistent with assumptions made in consensus standards such as the National Electrical Safety Code (IEEE C2-2012). The more conservative value accounts for variables such as electrode shape, wave shape, and a certain amount of overvoltage. |
| 7The detailed design of a circuit interrupter, such as the design of the contacts, resistor insertion, and breaker timing control, are beyond the scope of this appendix. The design of the system generally accounts for these features. This appendix only discusses features that can limit the maximum switching transient overvoltage on a system. |
| 8Surge arrester application is beyond the scope of this appendix. However, if the employer installs the arrester near the worksite, the application would be similar to the protective gaps discussed in paragraph IV.D of this appendix. |
| 9The employer should check the withstand voltage to ensure that it results in a probability of gap flashover that is acceptable from a system outage perspective. (In other words, a gap sparkover will produce a system outage. The employer should determine whether such an outage will impact overall system performance to an acceptable degree.) In general, the withstand voltage should be at least 1.25 times the maximum crest operating voltage. |
| 10The manufacturer of the gap provides, based on test data, the critical sparkover voltage for each gap spacing (for example, a critical sparkover voltage of 665 kilovolts for a gap spacing of 1.2 meters). The withstand voltage for the gap is equal to 85 percent of its critical sparkover voltage. |
| 11Switch steps 1 and 2 if the length of the protective gap is known. |
| 12IEEE Std 516-2009 states that most employers add 0.2 to the calculated value of T as an additional safety factor. |
| 13To eliminate sparkovers due to minor system disturbances, the employer should use a withstand voltage no lower than 1.25 p.u. Note that this is a practical, or operational, consideration only. It may be feasible for the employer to use lower values of withstand voltage. |