HTML has links - PDF has Authentication
51-51-1503  <<  51-51-1504 >>   51-51-1505

PDFWAC 51-51-1504

Section 1504Exhaust ducts and exhaust openings.

M1504.3 Exhaust openings. Air exhaust openings shall terminate as follows:
1. Not less than 3 feet (914 mm) from property lines.
2. Not less than 3 feet (914 mm) from gravity air intake openings, operable windows and doors.
3. Not less than 10 feet (3048 mm) from mechanical air intake openings except where either of the following apply:
3.1. The exhaust opening is located not less than 3 feet (914 mm) above the air intake opening.
3.2. The exhaust opening is part of a factory-built intake/exhaust combination termination fitting installed in accordance with the manufacturer's instructions, and the exhaust air is drawn from a living space.
4. Openings shall comply with Sections R303.5.2 and R303.6.
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-03-023, § 51-51-1504, filed 1/6/20, effective 7/1/20.]
Site Contents
Selected content listed in alphabetical order under each group