Search
51-51-0317  <<  51-51-0325 >>   51-51-0326

(Effective Until July 1, 2010.)

WAC 51-51-0325

Agency filings affecting this section

Section R325 — Adult family homes.

  


SECTION R325

ADULT FAMILY HOMES


R325.1 General. This section shall apply to all newly constructed adult family homes and all existing single family homes being converted to adult family homes. This section shall not apply to those adult family homes licensed by the state of Washington department of social and health services prior to July 1, 2001.


R325.2 Submittal Standards. In addition to those requirements in Section 106.1, the submittal shall identify the project as a Group R-3 Adult Family Home Occupancy. A floor plan shall be submitted identifying the means of egress and the components in the means of egress such as stairs, ramps, platform lifts and elevators. The plans shall indicate the rooms used for clients and the sleeping room classification of each room.


R325.3 Sleeping Room Classification. Each sleeping room in an adult family home shall be classified as:

     1. Type S - where the means of egress contains stairs, elevators or platform lifts.

     2. Type NS1 - where one means of egress is at grade level or a ramp constructed in accordance with R311.6 is provided.

     3. Type NS2 - where two means of egress are at grade level or ramps constructed in accordance with R311.6 are provided.


R325.4 Types of Locking Devices. All bedroom and bathroom doors shall be openable from the outside when locked.

     Every closet shall be readily openable from the inside.


R325.5 Smoke Alarm Requirements. All adult family homes shall be equipped with smoke alarms installed as required in Section R313. Alarms shall be installed in such a manner so that the fire warning may be audible in all parts of the dwelling upon activation of a single device.


R325.6 Escape Windows and Doors. Every sleeping room shall be provided with emergency escape and rescue windows as required by Section R310. No alternatives to the sill height such as steps, raised platforms or other devices placed by the openings will be approved as meeting this requirement.


R325.7 Fire Apparatus Access Roads and Water Supply for Fire Protection. Adult family homes shall be served by fire apparatus access roads and water supplies meeting the requirements of the local jurisdiction.



[Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-090, § 51-51-0325, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-109, § 51-51-0325, filed 12/17/03, effective 7/1/04.]






(Effective July 1, 2010.)

WAC 51-51-0325

Section R325 — Adult family homes.

  



SECTION R325

ADULT FAMILY HOMES


R325.1 General. This section shall apply to all newly constructed adult family homes and all existing single family homes being converted to adult family homes. This section shall not apply to those adult family homes licensed by the state of Washington department of social and health services prior to July 1, 2001.


R325.2 Submittal Standards. In addition to those requirements in Section 106.1, the submittal shall identify the project as a Group R-3 Adult Family Home Occupancy. A floor plan shall be submitted identifying the means of egress and the components in the means of egress such as stairs, ramps, platform lifts and elevators. The plans shall indicate the rooms used for clients and the sleeping room classification of each room.


R325.3 Sleeping Room Classification. Each sleeping room in an adult family home shall be classified as:

     1. Type S - where the means of egress contains stairs, elevators or platform lifts.

     2. Type NS1 - where one means of egress is at grade level or a ramp constructed in accordance with R325.9 is provided.

     3. Type NS2 - where two means of egress are at grade level or ramps constructed in accordance with R325.9 are provided.


R325.4 Types of Locking Devices. All bedroom and bathroom doors shall be openable from the outside when locked.

     Every closet shall be readily openable from the inside.

     Operable parts of door handles, pulls, latches, locks and other devices installed in adult family homes shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist. The force required to activate operable parts shall be 5.0 pounds (22.2 N) maximum. Exit doors shall have no additional locking devices.


R325.5 Smoke Alarm Requirements. All adult family homes shall be equipped with smoke alarms installed as required in Section R313. Alarms shall be installed in such a manner so that the fire warning may be audible in all parts of the dwelling upon activation of a single device.


R325.6 Escape Windows and Doors. Every sleeping room shall be provided with emergency escape and rescue windows as required by Section R310. No alternatives to the sill height such as steps, raised platforms or other devices placed by the openings will be approved as meeting this requirement.


R325.7 Fire Apparatus Access Roads and Water Supply for Fire Protection. Adult family homes shall be served by fire apparatus access roads and water supplies meeting the requirements of the local jurisdiction.


R325.8 Grab Bars. Grab bars shall be installed for all water closets and bathtubs and showers. The grab bars shall comply with ICC/ANSI A117.1 Sections 604.5 and 607.4 and 608.3.


EXCEPTION: Grab bars are not required for water closets and bathtubs and showers used exclusively by staff of the adult family home.

R325.9 Ramps. All interior and exterior ramps, when provided, shall be constructed in accordance with Section R311.6 with a maximum slope of 1 vertical to 12 horizontal. The exception to R
311.6.1 is not allowed for adult family homes. Handrails shall be installed in accordance with R325.9.1.


R325.9.1 Handrails for Ramps. Handrails shall be installed on both sides of ramps between the slope of 1 vertical to 12 horizontal and 1 vertical and 20 horizontal in accordance with R311.6.3.1 through R311.6.3.3.


R325.10 Stair Treads and Risers. Stair treads and risers shall be constructed in accordance with R311.5.3.2. Handrails shall be installed in accordance with R325.10.1.


R325.10.1 Handrails for Treads and Risers. Handrails shall be installed on both sides of treads and risers numbering from one riser to multiple risers. Handrails shall be installed in accordance with R311.5.6.1 through R311.5.6.3.



[Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 09-04-023, § 51-51-0325, filed 1/27/09, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-090, § 51-51-0325, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-109, § 51-51-0325, filed 12/17/03, effective 7/1/04.]