HTML has links - PDF has Authentication
296-45-903  <<  296-45-905 >>   296-45-906

PDFWAC 296-45-905

Appendix CMethods of inspecting and testing wood polesNonmandatory.

I. Introduction
When employees are to perform work on a wood pole, it is important to determine the condition of the pole before employees climb it. The weight of the employee, the weight of equipment to be installed, and other working stresses (such as the removal or retensioning of conductors) can lead to the failure of a defective pole or a pole that is not designed to handle the additional stresses.(1) For these reasons, it is essential that, before an employee climbs a wood pole, the employer ascertains that the pole is capable of sustaining the stresses of the work. The determination that the pole is capable of sustaining these stresses includes an inspection of the condition of the pole.
Footnote(1)
If the employer finds the pole to be unsafe to climb or to work from, the employer must secure the pole so that it does not fail while an employee is on it.
 
The employer can secure the pole by a line truck boom, by ropes or guys, or by lashing a new pole alongside it. If a new one is lashed alongside the defective pole, employees should work from the new one.
II. Inspection of wood poles
A qualified electrical employee should inspect wood poles for the following conditions:(2)
Footnote(2)
The presence of any of these conditions is an indication that the pole may not be safe to climb or to work from. The employee performing the inspection must be qualified to make a determination as to whether or not it is safe to perform the work without taking additional precautions.
A. General condition.
Buckling at the ground line or an unusual angle with respect to the ground may indicate that the pole has rotted or is broken.
B. Cracks.
Horizontal cracks perpendicular to the grain of the wood may weaken the pole. Vertical cracks, although not normally considered to be a sign of a defective pole, can pose a hazard to the climber, and the employee should keep his or her gaffs away from them while climbing.
C. Holes.
Hollow spots and woodpecker holes can reduce the strength of a wood pole.
D. Shell rot and decay.
Rotting and decay are cutout hazards and are possible indications of the age and internal condition of the pole.
E. Knots.
One large knot or several smaller ones at the same height on the pole may be evidence of a weak point on the pole.
F. Depth of setting.
Evidence of the existence of a former ground line substantially above the existing ground level may be an indication that the pole is no longer buried to a sufficient extent.
G. Soil conditions.
Soft, wet, or loose soil around the base of the pole may indicate that the pole will not support any change in stress.
H. Burn marks.
Burning from transformer failures or conductor faults could damage the pole so that it cannot withstand changes in mechanical stress.
III. Testing of wood poles
The following tests are recognized as acceptable methods of testing wood poles:
A. Hammer test.
Rap the pole sharply with a hammer weighing about 3 pounds (1.4 kg), starting near the ground line and continuing upwards circumferentially around the pole to a height of approximately 6 feet (1.8 meters). The hammer will produce a clear sound and rebound sharply when striking sound wood. Decay pockets will be indicated by a dull sound or a less pronounced hammer rebound. Also, prod the pole as near the ground line as possible using a pole prod or a screwdriver with a blade at least 5 inches (127 millimeters) long. If substantial decay is present, the pole is unsafe.
B. Rocking test.
Apply a horizontal force to the pole and attempt to rock it back and forth in a direction perpendicular to the line. Exercise caution to avoid causing power lines to swing together. Apply the force to the pole either by pushing with a pike pole or pulling the pole with a rope. If the pole cracks during the test, it is unsafe.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060 and chapter 49.17 RCW. WSR 19-13-083, § 296-45-905, filed 6/18/19, effective 8/1/19; WSR 16-10-082, § 296-45-905, filed 5/3/16, effective 7/1/16. Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050 and [49.17].060. WSR 98-07-009, § 296-45-905, filed 3/6/98, effective 5/6/98.]
Site Contents
Selected content listed in alphabetical order under each group