Section R1002Masonry heaters.

R1002.2 Installation.Masonry heaters shall be installed in accordance with this section and shall be a masonry heater type approved by the department of ecology. Masonry heaters shall comply with one of the following:
1. Masonry heaters shall comply with the requirements of ASTM E 1602; or
2. Masonry heaters shall be listed and labeled in accordance with UL 1482 or CEN 15250 and installed in accordance with the manufacturer's installation instructions.
R1002.2.1 Combustion air and doors. Masonry heaters shall be provided with both of the following:
1. Primary combustion air ducted from the outside of the structure to the appliance.
2. Tight-fitting ceramic glass or metal doors. Flue dampers, when provided, shall have an external control and when in the closed position shall have a net free area of not less than five percent of the flue cross sectional area.
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 23-23-104, § 51-51-1002, filed 11/15/23, effective 3/16/24; WSR 16-03-025, § 51-51-1002, filed 1/11/16, effective 7/1/16. Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-068, § 51-51-1002, filed 2/1/13, effective 7/1/13.]