PROPOSED RULES
Original Notice.
Preproposal statement of inquiry was filed as WSR 04-13-073.
Title of Rule and Other Identifying Information: Amendment of chapter 51-11 WAC, Washington State Energy Code.
Hearing Location(s): Renton Holiday Inn Select, One South Grady Way, Renton, WA 98055-2500, on October 15, 2004, at 10:00 a.m.
Date of Intended Adoption: November 12, 2004.
Submit Written Comments to: Stan Price, Chair, Washington State Building Code Council, P.O. Box 42525, Olympia, WA 90504-2525 [98504-2525], e-mail sbcc@cted.wa.gov, fax (360) 586-9383, by October 15, 2004.
Assistance for Persons with Disabilities: Contact Sue Mathers by October 1, 2004, TTY (360) 753-7427 or (360) 725-2967.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The purpose of the proposed amendments is to amend the Washington State Energy Code to update mechanical efficiency requirements to the most recent national standards, to provide for new technology and building science in wall assemblies, to update wall and window thermal efficiency for energy savings and better consistency with national standards, to revise lighting allowances and controls for better consistency with national standards, to make additional allowances for use of isothermal humidification systems, to add efficiency requirements for small fan motors in series fan boxes, and to make editorial changes to the economizer section. These changes are proposed to increase energy efficiency, provide consistency with national standards, and provide clarification and flexibility.
1. Section 502.1.4.6, Wall Insulation:
Revises the section to add an exception for wall cavity to remain unfilled or partially filled in wall assemblies where insulation is provided on the outer surface of the assembly and full envelope calculations are performed.
| • | Technical improvement. |
| • | Improves flexibility. |
Revises Table 10-6 to correspond with new envelope requirements in Tables 13-1 and 13-2 in proposal #5. This proposal is linked to Proposal #5.
| • | Clarification. |
| • | Technical improvement. |
| • | Improves flexibility. |
Amends the exception to allow exposed elevated slab edges to remain uninsulated. This proposal is linked to Proposal #5.
| • | Energy savings potential: High. |
| • | Equivalent to national standard: ASHRAE/IESNA Standard 90.1-2001, Sections B-14 and D-17. |
4. Section 1330, Component Performance Option:
Eliminates the use of the 1989 version of EnvStd. This proposal is linked to Proposal #5.
| • | Energy savings potential: High. |
| • | Equivalent to national standard: ASHRAE/IESNA Standard 90.1-2001, Sections B-14 and D-17. |
Increases the thermal requirements for walls and glazing. Some of the proposed values are consistent with the national energy standard, ASHRAE/IESNA Standard 90.1-2001. Proposals 2, 3, and 4 are linked to this proposal.
| • | Energy savings potential: High. |
| • | Equivalent to national standard: ASHRAE/IESNA Standard 90.1-2001, Sections B-14 and D-17. |
Revises this section to allow the use of isothermal systems in certain situations where there is no energy savings with the use of adiabatic systems, and for small systems where an adiabatic system would be cost prohibitive.
| • | Technical improvement. |
| • | Improves flexibility. |
Provides alternate compliance options and clarifications.
1423: Expands simple system option to apply to all small cooling units.
1413.3: Corrects an error in the code section.
| • | Clarification. |
| • | Improves enforcement. |
| • | Improves flexibility. |
Option 1:
The term "individual fan-cooling units" was used in previous versions of the code and was inadvertently left out during all the editing of the previous economizer changes.
Option 2:
Increases the allowed capacity for units without economizer provided there is an increase in equipment efficiency.
| • | Clarification. |
| • | Technical improvement. |
| • | Improves flexibility. |
Adds efficiency requirements for small fan motors in series fan boxes.
| • | Energy savings potential: Medium. |
Revise minimum efficiencies for consistency with ASHRAE/IESNA Standard 90.1 Addendum I (Tables 14-1A, 1B) and addendum D (Table 14-1D).
| • | Equivalent to national standard: ASHRAE/IESNA Standard 90.1-2001, Addendums I and D. |
11. Sections 1513.6 and 1132.3, Automatic Lighting Controls:
Expands automatic shut-off control requirements to all nonresidential buildings over 5,000 square feet. Requires occupancy sensors for office areas less than 300 square feet.
| • | Energy savings potential: Medium. |
| • | Equivalent to national standard: ASHRAE/IESNA Standard 90.1-2001, Section 9.2.1.1. |
Table 15-1: Revises lighting power allowances for offices, schools and laboratories consistent with the national energy standard, ASHRAE/IESNA Standard 90.1-2001, Addendum G, Table 9.3.1.1.
Section 1521: Companion changes for consistency with changes to Table 15-1.
| • | Energy savings potential: Medium. |
| • | Equivalent to national standard: ASHRAE/IESNA Standard 90.1-2001, Addendum G, Table 9.3.1.1. |
Reasons Supporting Proposal: RCW 19.27A.025 and 19.27A.045.
Statutory Authority for Adoption: RCW 19.27A.025, 19.27A.045.
Statute Being Implemented: Chapters 19.27, 19.27A, and 34.05 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: The council is seeking comments on the issues proposed in the rules shown below.
Name of Proponent: State Building Code Council, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Krista Braaksma, P.O. Box 42525, Olympia, WA 98504-2525, (360) 725-2964; and Enforcement: Local jurisdictions.
No small business economic impact statement has been prepared under chapter 19.85 RCW. The proposed amendments have been reviewed by the Energy Code Technical Advisory Group and some were identified as having a cost impact on businesses required to comply with the rule. These costs were felt to be low to moderate increases in first cost on businesses required to comply. However, the increases do not represent a disproportionate cost to small business and if any additional first cost of construction is passed on to consumers, it will be completely offset by the consumer's energy savings. They are also offset by other cost saving proposals.
A cost-benefit analysis is not required under RCW 34.05.328. The State Building Code Council is not listed in this section as one of the agencies required to comply with this statute.
August 13, 2004
Tim Nogler
for Stan Price
Council Chair
OTS-7374.2
AMENDATORY SECTION(Amending WSR 04-01-106, filed 12/17/03,
effective 7/1/04)
WAC 51-11-0502
Building envelope requirements.
502.1 General:
502.1.1: The stated U- or F-factor of any component
assembly, listed in Table 5-1 or 5-2, such as roof/ceiling,
opaque wall or opaque floor may be increased and the U-factor
for other components decreased, provided that the total heat
gain or loss for the entire building envelope does not exceed
the total resulting from compliance to the U-factors specified
in this section.
The U-factors for typical construction assemblies are
included in Chapter 10. These values shall be used for all
calculations. Where proposed construction assemblies are not
represented in Chapter 10, values shall be calculated in
accordance with Chapters 23-30 in Standard RS-1 listed in
Chapter 7, using the framing factors listed in Chapter 10
where applicable.
For envelope assemblies containing metal framing, the
U-factor shall be determined by one of the following methods:
1. Results of laboratory or field measurements.
2. Standard RS-1, listed in Chapter 7, where the metal
framing is bonded on one or both sides to a metal skin or
covering.
3. The zone method as provided in Chapter 25 of Standard
RS-1, listed in Chapter 7.
4. Results of parallel path correction factors effective
framing/cavity R-values as provided in Table 10-5A - EFFECTIVE
R-VALUES FOR METAL FRAMING AND CAVITY ONLY for metal stud walls and
roof/ceilings.
502.1.2: For consideration of thermal mass effects, see
section 402.4.
502.1.3: When return air ceiling plenums are employed,
the roof/ceiling assembly shall:
a. For thermal transmittance purposes, not include the
ceiling proper nor the plenum space as part of the assembly;
and
b. For gross area purposes, be based upon the interior
face of the upper plenum surface.
502.1.4 Insulation:
502.1.4.1 General: All insulating materials shall comply
with sections 2603 and/or 719 of the International Building
Code. Substantial contact of the insulation with the surface
being insulated is required. All insulation materials shall
be installed according to the manufacturer's instructions to
achieve proper densities and maintain uniform R-values and
shall be installed in a manner which will permit inspection of
the manufacturer's R-value identification mark. To the
maximum extent possible, insulation shall extend over the full
component area to the intended R-value.
Alternatively, the thickness of roof/ceiling and wall
insulation that is either blown in or spray-applied shall be
identified by inches of thickness, density and R-value markers
installed at least one for every 300 square feet (28 m2)
through the attic, ceiling and/or wall space. In attics, the
markers shall be affixed to the trusses or joists and marked
with the minimum initial installed thickness and minimum
settled thickness with numbers a minimum 1.0 inch (25 mm) in
height. Each marker shall face the attic access. The
thickness of installed attic insulation shall meet or exceed
the minimum initial installed thickness shown by the marker. In cathedral ceilings and walls, the markers shall be affixed
to the rafter and wall frame at alternating high and low
intervals and marked with the minimum installed density and
R-value with numbers a minimum 1.0 inch (25 mm) in height. Each marker shall face the conditioned room area.
502.1.4.2 Insulation Materials: All insulation materials
including facings such as vapor barriers or breather papers
installed within floor/ceiling assemblies, roof/ceiling
assemblies, walls, crawl spaces, or attics shall have a flame
spread rating of less than 25 and a smoke density not to
exceed 450 when tested in accordance with ASTM E84-01.
[Statutory Authority: RCW 19.27A.020, 19.27A.045. 04-01-106,
§ 51-11-0502, filed 12/17/03, effective 7/1/04. Statutory
Authority: RCW 19.27A.025, 19.27A.045. 02-01-112, §
51-11-0502, filed 12/18/01, effective 7/1/02; 01-03-010, §
51-11-0502, filed 1/5/01, effective 7/1/01; 98-03-003, §
51-11-0502, filed 1/8/98, effective 7/1/98. Statutory
Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, § 51-11-0502, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, § 51-11-0502, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, §
51-11-0502, filed 12/19/91, effective 7/1/92. Statutory
Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, §
51-11-0502, filed 12/19/90, effective 7/1/91.] Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. TABLE 10-6 Frame Low-e(0.40),
Fixed Low-e(0.10),
Fixed Frame Frame Where a low-emissivity emittance is listed (i.e.: 0.40, 0.20, 0.10), that is the maximum allowed. Where a gas other than air is listed (i.e.: Argon), the gas fill shall be a minimum of 90%. Where an operator type is listed (i.e.: Fixed), the default is only allowed for that operator type. Where a frame type is listed (i.e.: Wood/vinyl), the default is only allowed for that frame type. Wood/vinyl frame includes
reinforced vinyl and aluminum-clad wood. TABLE 10-6A Thermal Break7 TABLE 10-6B1 THERMAL BREAK9 WOOD/REINFORCED VINYL10 Footnotes to Table 10-6B 3/8" = a minimum dead air space of 0.375 inches between the panes of glass. 1/2" = a minimum dead air space of 0.5 inches between the panes of glass. Product with air spaces different than those listed above shall use the value for the next smaller air space;
i.e. 3/4 inch = 1/2 inch U-factors, 7/16 inch = 3/8 inch U-factors, 5/16 inch = 1/4 inch U-factors. Low-e2 (emissivity) shall be 0.2 or less. Low-e1 (emissivity) shall be 0.1 or less. thermal break meeting the criteria in a) and b) above. TABLE 10-6C Glazing Glazing Glazing with 1/4 in. Airspace Glazing with 1/2 in. Airspace Glazing with e = 0.10, 1/2 in. Argon
EXCEPTIONS:
1. Foam plastic insulation shall comply with section 2603 of the International Building Code.
2. When such materials are installed in concealed spaces of Types III, IV and V construction, the flame
spread and smoke developed limitations do not apply to facing, provided that the facing is installed in
substantial contact with the unexposed surface of the ceiling, floor or wall finish.
3. Cellulose insulation shall comply with section 719 of the International Building Code.
502.1.4.3 Clearances: Where required, insulation shall
be installed with clearances according to manufacturer's
specifications. Insulation shall be installed so that
required ventilation is unobstructed. For blown or poured
loose fill insulation, clearances shall be maintained through
installation of a permanent retainer.
502.1.4.4 Access Hatches and Doors: Access doors from
conditioned spaces to unconditioned spaces (e.g., attics and
crawl spaces) shall be weatherstripped and insulated to a
level equivalent to the insulation on the surrounding
surfaces. Access shall be provided to all equipment which
prevents damaging or compressing the insulation. A wood
framed or equivalent baffle or retainer must be provided when
loose fill insulation is installed, the purpose of which is to
prevent the loose fill insulation from spilling into the
living space when the attic access is opened, and to provide a
permanent means of maintaining the installed R-value of the
loose fill insulation.
502.1.4.5 Roof/Ceiling Insulation: Open-blown or poured
loose fill insulation may be used in attic spaces where the
slope of the ceiling is not more than 3 feet in 12 and there
is at least 30 inches of clear distance from the top of the
bottom chord of the truss or ceiling joist to the underside of
the sheathing at the roof ridge. When eave vents are
installed, baffling of the vent openings shall be provided so
as to deflect the incoming air above the surface of the
insulation. Baffles shall be, rigid material, resistant to
wind driven moisture. Requirements for baffles for ceiling
insulation shall meet the International Building Code section
1203.2 for minimum ventilation requirements. When feasible,
the baffles shall be installed from the top of the outside of
the exterior wall, extending inward, to a point 6 inches
vertically above the height of noncompressed insulation, and
12 inches vertically above loose fill insulation.
502.1.4.6 Wall Insulation: Insulation installed in
exterior walls shall comply with the provisions of this
section. All wall insulation shall fill the entire framed
cavity. Exterior wall cavities isolated during framing shall
be fully insulated to the levels of the surrounding walls. All faced insulation shall be face stapled to avoid
compression.
EXCEPTION:
Framed cavity can be empty or partially filled provided:
1. The wall assembly calculations are performed along with a completed performance calculation for
the whole building; and
2. Insulation installed in partially filled cavities is not included in the performance calculation.
502.1.4.7 Floor Insulation: Floor insulation shall be
installed in a permanent manner in substantial contact with
the surface being insulated. Insulation supports shall be
installed so spacing is no more than 24 inches on center. Foundation vents shall be placed so that the top of the vent
is below the lower surface of the floor insulation.
EXCEPTION:
Insulation may be omitted from floor areas over heated basements, heated garages or underfloor areas
used as HVAC supply plenums. When foundation walls are insulated, the insulation shall be attached in
a permanent manner. The insulation shall not block the airflow through foundation vents when
installed. When foundation vents are not placed so that the top of the vent is below the lower surface
of the floor insulation, a permanently attached baffle shall be installed at an angle of 30° from
horizontal, to divert air flow below the lower surface of the floor insulation.
502.1.4.8 Slab-On-Grade: Slab-on-grade insulation,
installed inside the foundation wall, shall extend downward
from the top of the slab for a minimum distance of 24 inches
or downward and then horizontally beneath the slab for a
minimum combined distance of 24 inches. Insulation installed
outside the foundation shall extend downward to a minimum of
24 inches or to the frostline. Above grade insulation shall
be protected.
EXCEPTION:
For monolithic slabs, the insulation shall extend downward from the top of the slab to the bottom of
the footing.
502.1.4.9 Radiant Slabs: The entire area of a radiant
slab shall be thermally isolated from the soil, with a minimum
of R-10 insulation. The insulation shall be an approved
product for its intended use. If a soil gas control system is
present below the radiant slab, which results in increased
convective flow below the radiant slab, the radiant slab shall
be thermally isolated from the sub-slab gravel layer.
502.1.4.10 Below Grade Walls: Below grade exterior wall
insulation used on the exterior (cold) side of the wall shall
extend from the top of the below grade wall to the top of the
footing and shall be approved for below grade use. Above
grade insulation shall be protected.
Insulation used on the interior (warm) side of the wall
shall extend from the top of the below grade wall to the below
grade floor level.
502.1.5 Glazing and Door U-factors: Glazing and door
U-factors shall be determined in accordance with sections
502.1.5.1 and 502.1.5.2. All products shall be labeled with
the NFRC certified or default U-factor. The labeled U-factor
shall be used in all calculations to determine compliance with
this Code. Sealed insulating glass shall conform to, or be in
test for, ASTM E-774-81 class A.
EXCEPTIONS:
1. For glazed wall systems, assemblies with all of the following features are deemed to satisfy the
vertical glazing U-factor requirement in Table 6-1 or 6-2 options with vertical glazing U-0.40 and
greater:
a. Double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e = 0.10
maximum, with 90% minimum argon gas fill, and a non-aluminum spacer (as defined in footnote 1 to
Table 10-6B), and
b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum
clad wood, vinyl, aluminum clad vinyl, or reinforced vinyl.
The only labeling requirement for products using this exception shall be a description of the product
and a label stating: "This product is deemed to satisfy the Table 6-1 or 6-2 vertical glazing U-factor
requirement using the exception to Section 502.1.5 in the Washington State Energy Code."
2. For overhead glazing, assemblies with all of the following features are deemed to satisfy the overhead
glazing U-factor requirement in Table 6-1 or 6-2 options except the unlimited glazing area options
(Options IV and V in Table 6-1 and Options V and VI in Table 6-2):
a. Either, double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e
=0.20 maximum, with 90% minimum argon gas fill, or, triple glazed plastic domes, and
b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum
clad wood, vinyl, aluminum clad vinyl, or reinforced vinyl.
The only labeling requirement for products using this exception shall be a description of the product
and a label stating: "This product is deemed to satisfy the Table 6-1 or 6-2 overhead glazing U-factor
requirement using the exception to Section 502.1.5 in the Washington State Energy Code."
3. For solariums with a floor area which does not exceed 300 square feet, assemblies which comply with
the features listed in exception 2 are deemed to satisfy the vertical glazing and overhead glazing
U-factor requirement in Table 6-1 or 6-2 options with vertical glazing U-0.40 and greater.
The only labeling requirement for products using this exception shall be a description of the product
and a label stating: "This product is deemed to satisfy the Table 6-1 or 6-2 vertical glazing and
overhead glazing U-factor requirements using the exception to Section 502.1.5 in the Washington
State Energy Code."
502.1.5.1 Standard Procedure for Determination of Glazing
U-factors: U-factors for glazing shall be determined,
certified and labeled in accordance with the National
Fenestration Rating Council (NFRC) Product Certification
Program (PCP), as authorized by an independent certification
and inspection agency licensed by the NFRC. Compliance shall
be based on the Residential Model Size. Product samples used
for U-factor determinations shall be production line units or
representative of units as purchased by the consumer or
contractor. Products that are listed in the NFRC Certified
Products Directory or certified to the NFRC standard shall not
use default values.
EXCEPTIONS:
1. Glazing products without NFRC ratings may be assigned default U-factors from Table 10-6A for
vertical glazing and from Table 10-6E for overhead glazing.
2. Units without NFRC ratings produced by a small business may be assigned default U-factors from
Table 10-6A for garden windows, from Table 10-6B for other vertical glazing, and from Table 10-6E
for overhead glazing.
502.1.5.2 Standard Procedure for Determination of Door
U-factors: All doors, including fire doors, shall be assigned
default U-factors from Table 10-6C.
EXCEPTIONS:
1. U-factors determined, certified and labeled in accordance with the National Fenestration Rating
Council (NFRC) Product Certification Program (PCP), as authorized by an independent certification
and inspection agency licensed by the NFRC.
2. The default values for the opaque portions of doors shall be those listed in Table 10-6C, provided
that the U-factor listed for a door with a thermal break shall only be allowed if both the door and the
frame have a thermal break.
3. One unlabeled or untested exterior swinging door with the maximum area of 24 square feet may be
installed for ornamental, security or architectural purposes. Products using this exception shall not be
included in the U-factor calculation requirements, however glazing area shall be included in glazing area
calculations.
502.1.6 Moisture Control:
502.1.6.1 Vapor Retarders: Vapor retarders shall be
installed on the warm side (in winter) of insulation as
specified in the following cases.
EXCEPTION:
Vapor retarder installed with not more than 1/3 of the nominal R-value between it and the conditioned
space.
502.1.6.2 Floors: Floors separating conditioned space
from unconditioned space shall have a vapor retarder
installed. The vapor retarder shall have a one perm dry cup
rating or less (i.e., four mil [0.004 inch thick] polyethylene
or kraft faced material).
502.1.6.3 Roof/Ceilings: Roof/ceiling assemblies where
the ventilation space above the insulation is less than an
average of 12 inches shall be provided with a vapor retarder. Faced batt insulation where used as a vapor retarder shall be
face stapled. Single rafter joist vaulted ceiling cavities
shall be of sufficient depth to allow a minimum one inch
vented air space above the insulation.
502.1.6.4: Vapor retarders shall not be required in
roof/ceiling assemblies where the ventilation space above the
insulation averages 12 inches or greater.
502.1.6.5: Vapor retarders shall not be required where
all of the insulation is installed between the roof membrane
and the structural roof deck.
502.1.6.6 Walls: Walls separating conditioned space from
unconditioned space shall have a vapor retarder installed. Faced batt insulation shall be face stapled.
502.1.6.7 Ground Cover: A ground cover of six mil (0.006
inch thick) black polyethylene or approved equal shall be laid
over the ground within crawl spaces. The ground cover shall
be overlapped 12 inches minimum at the joints and shall extend
to the foundation wall.
EXCEPTION:
The ground cover may be omitted in crawl spaces if the crawl space has a concrete slab floor with a
minimum thickness of 3-1/2 inches.
502.2 Thermal Criteria for Group R Occupancy:
502.2.1 UA Calculations: The proposed UA as calculated
using Equations 2 and 3 shall not exceed the target UA as
calculated using Equation 1. For the purpose of determining
equivalent thermal performance, the glazing area for the
target UA shall be calculated using values in Table 5-1. The
opaque door area shall be the same in the target UA and the
proposed UA.
EXCEPTION:
Log and solid timber walls that have a minimum average thickness of 3.5" and with space heat type
other than electric resistance, are exempt from wall target UA and proposed UA calculations.
502.2.2 Space Heat Type: The following two categories
comprise all space heating types:
1. Electric Resistance: Space heating systems which
include baseboard units, radiant units and forced air units as
either the primary or secondary heating system.
EXCEPTION:
Electric resistance systems for which the total electric heat capacity in each individual dwelling unit
does not exceed the greater of: 1) One thousand watts (1000 w) per dwelling unit, or; 2) One watt per
square foot (1 w/ft2) of the gross floor area.
2. Other: All gas, wood, oil and propane space heating
systems, unless electric resistance is used as a secondary
heating system, and all heat pump space heating systems. (See
EXCEPTIONS, Electric Resistance, section 502.2.2 above.)
502.3 Reserved.
502.4 Air Leakage:
502.4.1 General: The requirements of this section shall
apply to all buildings and structures, or portions thereof,
and only to those locations separating outdoor ambient
conditions from interior spaces that are heated or
mechanically cooled.
502.4.2 Doors and Windows, General: Exterior doors and
windows shall be designed to limit air leakage into or from
the building envelope. Site-constructed doors and windows
shall be sealed in accordance with Section 502.4.3.
502.4.3 Seals and Weatherstripping:
a. Exterior joints around windows and door frames,
openings between walls and foundation, between walls and roof
and wall panels; openings at penetrations of utility services
through walls, floors and roofs; and all other openings in the
building envelope for all occupancies and all other openings
in between units in R-1 and R-2 Occupancy shall be sealed,
caulked, gasketed or weatherstripped to limit air leakage. Other exterior joints and seams shall be similarly treated, or
taped, or covered with moisture vapor permeable housewrap.
b. All exterior doors or doors serving as access to an
enclosed unheated area shall be weatherstripped to limit
leakage around their perimeter when in a closed position.
c. Site built windows are exempt from testing but shall
be made tight fitting. Fixed lights shall have glass retained
by stops with sealant or caulking all around. Operating sash
shall have weatherstripping working against overlapping trim
and a closer/latch which will hold the sash closed. The
window frame to framing crack shall be made tight with
caulking, overlapping membrane or other approved technique.
d. Openings that are required to be fire resistive are
exempt from this section.
502.4.4 Recessed Lighting Fixtures: When installed in
the building envelope, recessed lighting fixtures shall meet
one of the following requirements:
1. Type IC rated, manufactured with no penetrations
between the inside of the recessed fixture and ceiling cavity
and sealed or gasketed to prevent air leakage into the
unconditioned space.
2. Type IC rated, installed inside a sealed box
constructed from a minimum 1/2 inch thick gypsum wall board,
or constructed from a preformed polymeric vapor barrier, or
other air tight assembly manufactured for this purpose.
3. Type IC rated, certified under ASTM E283 to have no
more than 2.0 cfm air movement from the conditioned space to
the ceiling cavity. The lighting fixture shall be tested at
75 Pascals or 1.57 lbs/ft2 pressure difference and have a label
attached, showing compliance.
AMENDATORY SECTION(Amending WSR 02-01-112, filed 12/18/01,
effective 7/1/02)
WAC 51-11-1006
Section 1006 Default U-factors for
glazing and doors.
1006.1 Glazing and Doors without NFRC Certification:
Glazing and doors that do not have NFRC certification shall be
assigned the following U-factors:
Other than Group R Occupancy: DEFAULT U-FACTORS
FOR VERTICAL GLAZING, OVERHEAD GLAZING AND
OPAQUE DOORS
Vertical Glazing
U-Factor
Any
Frame
Aluminum
W/Thermal
Break
Vinyl/Wood
Single
1.45
1.45
1.45
Double
0.90
0.85
0.75
1/2 Inch Air,
Fixed
0.75
0.70
0.60
1/2 Inch Air,
0.60
0.55
0.50
1/2 Inch Air,
Low-e(0.10),
Fixed
0.55
0.50
0.45
1/2 Inch
Argon,
0.50
0.45
0.40
The category for aluminum frame with a thermal break is as
defined in footnote 7 to Table 10-6A.
((
Overhead GlazingU-FactorAny FrameVinyl/WoodSingle2.152.15Double1.451.00Low-e(0.40) or Argon1.400.95Low-e(0.40) + Argon1.300.85Low-e(0.20) Air1.300.90Low-e(0.20) + Argon1.250.80Triple1.250.80))Overhead Glazing: Sloped Glazing (Including Frame)
U-Factor
Any
Frame
Aluminum
W/Thermal
Break
Vinyl/Wood
Single
1.74
1.74
1.74
Double
1.08
1.02
0.90
1/2 Inch Air,
Fixed
0.90
0.84
0.72
1/2 Inch Air,
Low-e(0.40),
Fixed
0.72
0.66
0.60
1/2 Inch Air,
Low-e(0.10),
Fixed
0.66
0.60
0.54
1/2 Inch
Argon,
Low-e(0.10),
Fixed
0.60
0.54
0.48
This default table is applicable to sloped glazing only.
(Sloped glazing is a multiple-lite glazed system (similar to a
curtain wall) that is mounted at a slope greater than 15° from
the vertical plane.) Other overhead glazing shall use the
defaults in Table 10-6E.
Opaque Doors
U-Factor
Uninsulated Metal
1.20
Insulated Metal (Including Fire Door and
Smoke Vent)
0.60
Wood
0.50
Notes:
Where a gap width is listed (i.e.: 1/2 inch), that is the minimum allowed.
Group R Occupancy: DEFAULT U-FACTORS FOR VERTICAL GLAZING
Description1,2,3,4
Frame Type5,6
Aluminum
Aluminum
Wood/Vinyl
Windows
Single
1.20
1.20
1.20
Double, < 1/2"
Clear
0.92
0.75
0.63
Clear + Argon
0.87
0.71
0.60
Low-e
0.85
0.69
0.58
Low-e + Argon
0.79
0.62
0.53
Double, > 1/2"
Clear
0.86
0.69
0.58
Clear + Argon
0.83
0.67
0.55
Low-e
0.78
0.61
0.51
Low-e + Argon
0.75
0.58
0.48
Triple,
Clear
0.70
0.53
0.43
Clear + Argon
0.69
0.52
0.41
Low-e
0.67
0.49
0.40
Low-e + Argon
0.63
0.47
0.37
Garden
Single
2.60
n.a.
2.31
Windows
Double
Clear
1.81
n.a.
1.61
Clear + Argon
1.76
n.a.
1.56
Low-e
1.73
n.a.
1.54
Low-e + Argon
1.64
n.a.
1.47
1
<1/2" = a minimum dead air space of less than 0.5 inches between the panes of glass.
> 1/2" = a minimum dead air space of 0.5 inches or greater between the panes of glass.
Where no gap width is listed, the minimum gap width is 1/4".
2
Any low-e (emissivity) coating (0.1, 0.2 or 0.4).
3
U-factors listed for argon shall consist of sealed, gas-filled insulated units for argon, C02, SF6, argon/SF6
mixtures and Krypton.
4
"Glass block” assemblies may use a U-factor of 0.51.
5
Insulated fiberglass framed products shall use wood/vinyl U-factors.
6
Aluminum clad wood windows shall use the U-factors listed for wood/vinyl windows.
7
Aluminum Thermal Break = An aluminum thermal break framed window shall incorporate the following
minimum design characteristics:
a)
The thermal conductivity of the thermal break material shall be not more than 3.6 Btu-in/h/ft2/°F;
b)
The thermal break material must produces a gap in the frame material of not less than 0.210 inches; and,
c)
All metal framing members of the products exposed to interior and exterior air shall incorporate a
thermal break meeting the criteria in a) and b) above.
Group R Occupancy: SMALL BUSINESS COMPLIANCE TABLE FOR VERTICAL GLAZING
FRAME TYPE7,8
DESCRIPTION2,3,4,6
ALUMINUM
ALUM.
WOOD/VINYL
ALUM. CLAD
Double, Clear 1/4"
0.82
0.66
0.56
0.59
Double, Clear 1/4" + argon
0.77
0.63
0.53
0.56
Double, Low-e4 1/4"
0.76
0.61
0.52
0.54
Double, Low-e2 1/4"
0.73
0.58
0.49
0.51
Double, Low-e1 1/4"
0.70
0.55
0.47
0.49
Double, Low-e4 1/4" + argon
0.70
0.55
0.47
0.49
Double, Low-e2 1/4" + argon
0.66
0.52
0.43
0.46
Double, Low-e1 1/4" + argon
0.64
0.50
0.41
0.43
Double, Clear 3/8"
0.78
0.63
0.54
0.57
Double, Clear 3/8" + argon
0.75
0.60
0.51
0.54
Double, Low-e4 3/8"
0.72
0.57
0.48
0.51
Double, Low-e2 3/8"
0.69
0.54
0.45
0.48
Double, Low-e1 3/8"
0.66
0.51
0.43
0.46
Double, Low-e4 3/8" + argon
0.68
0.53
0.44
0.47
Double, Low-e2 3/8" + argon
0.63
0.49
0.41
0.44
Double, Low-e1 3/8" + argon
0.61
0.47
0.39
0.41
Double, Clear 1/2"
0.75
0.60
0.50
0.54
Double, Clear 1/2" + argon
0.72
0.58
0.48
0.51
Double, Low-e4 1/2"
0.68
0.53
0.44
0.47
Double, Low-e2 1/2"
0.64
0.50
0.40
0.44
Double, Low-e1 1/2"
0.61
0.47
0.35
0.42
Double, Low-e4 1/2" + argon
0.65
0.50
0.42
0.44
Double, Low-e2 1/2" + argon
0.60
0.46
0.37
0.40
Double, Low-e1 1/2" + argon
0.58
0.43
0.35
0.38
Triple, Clear 1/4"
0.66
0.52
0.42
0.44
Triple, Clear 1/4" + argon
0.63
0.49
0.39
0.42
Triple, Low-e4 1/4"
0.64
0.50
0.40
0.40
Triple, Low-e2 1/4"
0.62
0.48
0.39
0.41
Triple, Low-e1 1/4"
0.61
0.47
0.38
0.40
Triple, Low-e4 1/4" + argon
0.60
0.46
0.37
0.39
Triple, Low-e2 1/4" + argon
0.58
0.43
0.34
0.37
Triple, Low-el 1/4" + argon
0.57
0.42
0.34
0.36
Triple, Clear 1/2"
0.61
0.46
0.37
0.40
Triple, Clear 1/2" + argon
0.59
0.45
0.36
0.38
Triple, Low-e4 1/2"
0.58
0.43
0.35
0.37
Triple, Low-e2 1/2"
0.55
0.41
0.32
0.35
Triple, Low-e1 1/2"
0.54
0.39
0.31
0.33
Triple, Low-e4 1/2" + argon
0.55
0.41
0.32
0.35
Triple, Low-e2 1/2" + argon
0.52
0.38
0.30
0.32
Triple, Low-e1 1/2" + argon
0.51
0.37
0.29
0.31
1
Subtract 0.02 from the listed default U-factor for nonaluminum spacer. Acceptable spacer materials may
include but is not limited to fiberglass, wood and butyl or other material with an equivalent thermal
performance.
2
1/4" = a minimum dead air space of 0.25 inches between the panes of glass.
3
Low-e4 (emissivity) shall be 0.4 or less.
4
U-factors listed for argon shall consist of sealed, gas-filled insulated units for argon, CO2, SF6, and
argon/SF6 mixtures. The following conversion factor shall apply to Krypton gas-filled units: 1/4" or
greater with krypton is equivalent to 1/2" argon.
5
Reserved.
6
"Glass block” assemblies may use a U-factor of 0.51.
7
Insulated fiberglass framed products shall use wood/vinyl U-factors.
8
Subtract 0.02 from the listed default values for solariums.
9
Aluminum Thermal Break = An aluminum thermal break framed window shall incorporate the following
minimum design characteristics:
a)
The thermal conductivity of the thermal break material shall be not more than 3.6 Btu-in/h/ft2/F°;
b)
The thermal break material must produce a gap in the frame material of not less than 0.210 inches; and,
c)
All metal framing members of the products exposed to interior and exterior air shall incorporate a
10
Aluminum clad wood windows shall use the U-factors listed for Aluminum Clad Wood/Reinforced Vinyl
windows. Vinyl clad wood window shall use the U-factors listed for Wood/Vinyl windows. Any vinyl
frame window with metal reinforcement in more than one rail shall use the U-factors listed for Aluminum
Clad Wood/Reinforced Vinyl window.
Group R Occupancy: DEFAULT U-FACTORS FOR DOORS
Door Type
No
Single
Double
Double
Double
SWINGING DOORS (Rough opening - 38 in. x 82 in.)
Slab Doors
Wood slab in wood framea
0.46
6% glazing (22 in. x 8 in. lite)
-
0.48
0.47
0.46
0.44
25% glazing (22 in. x 36 in. lite)
-
0.58
0.48
0.46
0.42
45% glazing (22 in. x 64 in. lite)
-
0.69
0.49
0.46
0.39
More than 50% glazing
Use Table 10-6A
Insulated steel slab with wood edge in
wood framea
0.16
6% glazing (22 in. x 8 in. lite)
-
0.21
0.20
0.19
0.18
25% glazing (22 in. x 36 in. lite)
-
0.39
0.28
0.26
0.23
45% glazing (22 in. x 64 in. lite)
-
0.58
0.38
0.35
0.26
More than 50% glazing
Use Table 10-6A
Foam insulated steel slab with metal edge in
steel frameb
0.37
6% glazing (22 in. x 8 in. lite)
-
0.44
0.42
0.41
0.39
25% glazing (22 in. x 36 in. lite)
-
0.55
0.50
0.48
0.44
45% glazing (22 in. x 64 in. lite)
-
0.71
0.59
0.56
0.48
More than 50% glazing
Use Table 10-6A
Cardboard honeycomb slab with metal edge
in steel frameb
0.61
Style and Rail Doors
Sliding glass doors/French doors
Use Table 10-6A
Site-Assembled Style and Rail Doors
Aluminum in aluminum frame
-
1.32
0.99
0.93
0.79
Aluminum in aluminum frame with thermal
break
-
1.13
0.80
0.74
0.63
REVOLVING DOORS (Rough opening - 82 in. x 84 in.)
Aluminum in aluminum frame
Open
-
1.32
-
-
-
Closed
-
0.65
-
-
-
SECTIONAL OVERHEAD DOORS (Nominal - 10 ft x 10 ft)
Uninsulated steel (nominal U = 1.15)c
1.15
-
-
-
-
Insulated steel (nominal U = 0.11)c
0.24
-
-
-
-
Insulated steel with thermal break (nominal
U = 0.08)c
0.13
-
-
-
-
a.
Thermally broken sill (add 0.03 for nonthermally broken sill)
b.
Nonthermally broken sill
c.
Nominal U-factors are through the center of the insulated panel before consideration of thermal bridges
around the edges of the door sections and due to the frame.
Group R Occupancy: DEFAULT U-FACTORS FOR GLAZED DOORS
See Table 10-6C
| Frame Type | ||||
| Aluminum | Aluminum | Reinforced | Wood or Vinyl- | |
| Glazing Type | without | with | Vinyl/ | Clad Wood/ |
| Thermal | Thermal | Aluminum-Clad | Vinyl without | |
| Break | Break | Wood or Vinyl | Reinforcing | |
| Single Glazing | ||||
| glass | U-1.58 | U-1.51 | U-1.40 | U-1.18 |
| acrylic/polycarb | U-1.52 | U-1.45 | U-1.34 | U-1.11 |
| Double Glazing | ||||
| air | U-1.05 | U-0.89 | U-0.84 | U-0.67 |
| argon | U-1.02 | U-0.86 | U-0.80 | U-0.64 |
| Double Glazing, e = 0.20 | ||||
| air | U-0.96 | U-0.80 | U-0.75 | U-0.59 |
| argon | U-0.91 | U-0.75 | U-0.70 | U-0.54 |
| Double Glazing, e = 0.10 | ||||
| air | U-0.94 | U-0.79 | U-0.74 | U-0.58 |
| argon | U-0.89 | U-0.73 | U-0.68 | U-0.52 |
| Double Glazing, e = 0.05 | ||||
| air | U-0.93 | U-0.78 | U-0.73 | U-0.56 |
| argon | U-0.87 | U-0.71 | U-0.66 | U-0.50 |
| Triple Glazing | ||||
| air | U-0.90 | U-0.70 | U-0.67 | |