WSR 02-01-112

PERMANENT RULES

BUILDING CODE COUNCIL


[ Filed December 18, 2001, 3:46 p.m. , effective July 1, 2002 ]

     Date of Adoption: November 9, 2001.

     Purpose: To make changes to the Washington State Energy Code, chapter 51-11 WAC.

     Citation of Existing Rules Affected by this Order: Amending chapter 51-11 WAC, Sections 502, 503, 530, 533, 534, 535, 536, 537, 601, 602, 603, 625, 626, 627, 628, 629, 630, 900, 1006, 1401, 1411, 1412, 1413, 1423, 1433, 1437, 1452, and 1454.

     Statutory Authority for Adoption: RCW 19.27A.025, 19.27A.045.

      Adopted under notice filed as WSR 01-16-120 on July 31, 2001.

     Changes Other than Editing from Proposed to Adopted Version: 1. Section 530 (Table 5-1) was altered to provide a more permissive wall target component value for "Other Fuels."

     2. Section 602.2 was altered to reflect equivalent wall constructions to meet the R-21 requirement.

     3. Section 625 Option 1 was adopted for Tables 6-1 and 6-2.

     4. Section 1413.4 an exception was added to provide consistency with DOH rules for health care facilities.

     5. Sections 1423 and 1433 proposed change to further restrict units without economizers total capacity was not adopted.

     Number of Sections Adopted in Order to Comply with Federal Statute: New 0, Amended 0, Repealed 0; Federal Rules or Standards: New 0, Amended 0, Repealed 0; or Recently Enacted State Statutes: New 0, Amended 0, Repealed 0.

     Number of Sections Adopted at Request of a Nongovernmental Entity: New 0, Amended 28, Repealed 0.

     Number of Sections Adopted on the Agency's Own Initiative: New 0, Amended 0, Repealed 0.

     Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, Amended 0, Repealed 0.

     Number of Sections Adopted Using Negotiated Rule Making: New 0, Amended 0, Repealed 0;      Pilot Rule Making: New 0, Amended 0, Repealed 0; or Other Alternative Rule Making: New 0, Amended 28, Repealed 0.
     Effective Date of Rule: July 1, 2002.

December 18, 2001

Tim Nogler

for Jim Lewis

Council Chair

OTS-4961.4


AMENDATORY SECTION(Amending WSR 01-03-010, filed 1/5/01, effective 7/1/01)

WAC 51-11-0502   Building envelope requirements.  


     502.1 General:


     502.1.1: The stated U- or F-factor of any component assembly, listed in Table 5-1 or 5-2, such as roof/ceiling, opaque wall or opaque floor may be increased and the U-factor for other components decreased, provided that the total heat gain or loss for the entire building envelope does not exceed the total resulting from compliance to the U-factors specified in this Section.


     The U-factors for typical construction assemblies are included in Chapter 10. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Chapter 10, values shall be calculated in accordance with Chapters 21-29 in Standard RS-1 listed in Chapter 7, using the framing factors listed in Chapter 10 where applicable.


     For envelope assemblies containing metal framing, the U-factor shall be determined by one of the following methods:


     1. Results of laboratory or field measurements.


     2. Standard RS-25, listed in Chapter 7, where the metal framing is bonded on one or both sides to a metal skin or covering.


     3. The zone method as provided in Chapter 24 of Standard RS-1, listed in Chapter 7.


     4. Results of parallel path correction factors effective framing/cavity R-values as provided in Table 10-5A - EFFECTIVE R-VALUES FOR METAL FRAMING AND CAVITY ONLY for metal stud walls and roof/ceilings.


     502.1.2: For consideration of thermal mass effects, see section 402.4.


     502.1.3: When return air ceiling plenums are employed, the roof/ceiling assembly shall:


     a. For thermal transmittance purposes, not include the ceiling proper nor the plenum space as part of the assembly; and


     b. For gross area purposes, be based upon the interior face of the upper plenum surface.


     502.1.4 Insulation:


     502.1.4.1 General: All insulating materials shall comply with sections 2602 and/or 707 of the Uniform Building Code. Substantial contact of the insulation with the surface being insulated is required. All insulation materials shall be installed according to the manufacturer's instructions to achieve proper densities and maintain uniform R-values and shall be installed in a manner which will permit inspection of the manufacturer's R-value identification mark. To the maximum extent possible, insulation shall extend over the full component area to the intended R-value.


Alternatively, the thickness of roof/ceiling and wall insulation that is either blown in or spray-applied shall be identified by inches of thickness, density and R-value markers installed at least one for every 300 square feet (28 m2) through the attic, ceiling and/or wall space. In attics, the markers shall be affixed to the trusses or joists and marked with the minimum initial installed thickness and minimum settled thickness with numbers a minimum 1.0 inch (25 mm) in height. Each marker shall face the attic access. The thickness of installed attic insulation shall meet or exceed the minimum initial installed thickness shown by the marker. In cathedral ceilings and walls, the markers shall be affixed to the rafter and wall frame at alternating high and low intervals and marked with the minimum installed density and R-value with numbers a minimum 1.0 inch (25 mm) in height. Each marker shall face the conditioned room area.


     502.1.4.2 Insulation Materials: All insulation materials including facings such as vapor barriers or breather papers installed within floor/ceiling assemblies, roof/ceiling assemblies, walls, crawl spaces, or attics shall have a flame spread rating of less than 25 and a smoke density not to exceed 450 when tested in accordance with UBC Standard 8-1.


EXCEPTIONS: 1. Foam plastic insulation shall comply with section 2602 of the Uniform Building Code.
2. When such materials are installed in concealed spaces of Types III, IV and V construction, the flame spread and smoke developed limitations do not apply to facing, provided that the facing is installed in substantial contact with the unexposed surface of the ceiling, floor or wall finish.
3. Cellulose insulation shall comply with section 707 of the Uniform Building Code.

     502.1.4.3 Clearances: Where required, insulation shall be installed with clearances according to manufacturer's specifications. Insulation shall be installed so that required ventilation is unobstructed. For blown or poured loose fill insulation, clearances shall be maintained through installation of a permanent retainer.


     502.1.4.4 Access Hatches and Doors: Access doors from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces) shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding surfaces. Access shall be provided to all equipment which prevents damaging or compressing the insulation. A wood framed or equivalent baffle or retainer must be provided when loose fill insulation is installed, the purpose of which is to prevent the loose fill insulation from spilling into the living space when the attic access is opened, and to provide a permanent means of maintaining the installed R-value of the loose fill insulation.


     502.1.4.5 Roof/Ceiling Insulation: Open-blown or poured loose fill insulation may be used in attic spaces where the slope of the ceiling is not more than 3 feet in 12 and there is at least 30 inches of clear distance from the top of the bottom chord of the truss or ceiling joist to the underside of the sheathing at the roof ridge. When eave vents are installed, baffling of the vent openings shall be provided so as to deflect the incoming air above the surface of the insulation. Baffles shall be, rigid material, resistant to wind driven moisture. Requirements for baffles for ceiling insulation shall meet the Uniform Building Code section 1505.3 for minimum ventilation requirements. When feasible, the baffles shall be installed from the top of the outside of the exterior wall, extending inward, to a point 6 inches vertically above the height of noncompressed insulation, and 12 inches vertically above loose fill insulation.


     502.1.4.6 Wall Insulation: Insulation installed in exterior walls shall comply with the provisions of this section. All wall insulation shall fill the entire framed cavity. Exterior wall cavities isolated during framing shall be fully insulated to the levels of the surrounding walls. All faced insulation shall be face stapled to avoid compression.


     502.1.4.7 Floor Insulation: Floor insulation shall be installed in a permanent manner in substantial contact with the surface being insulated. Insulation supports shall be installed so spacing is no more than 24 inches on center. Foundation vents shall be placed so that the top of the vent is below the lower surface of the floor insulation.


EXCEPTION: Insulation may be omitted from floor areas over heated basements, heated garages or underfloor areas used as HVAC supply plenums. See Uniform Mechanical Code section 607 for underfloor supply plenum requirements. When foundation walls are insulated, the insulation shall be attached in a permanent manner. The insulation shall not block the airflow through foundation vents when installed. When foundation vents are not placed so that the top of the vent is below the lower surface of the floor insulation, a permanently attached baffle shall be installed at an angle of 30° from horizontal, to divert air flow below the lower surface of the floor insulation.

     502.1.4.8 Slab-On-Grade: Slab-on-grade insulation, installed inside the foundation wall, shall extend downward from the top of the slab for a minimum distance of 24 inches or downward and then horizontally beneath the slab for a minimum combined distance of 24 inches. Insulation installed outside the foundation shall extend downward to a minimum of 24 inches or to the frostline. Above grade insulation shall be protected.

EXCEPTION: For monolithic slabs, the insulation shall extend downward from the top of the slab to the bottom of the footing.

     502.1.4.9 Radiant Slabs: The entire area of a radiant slab shall be thermally isolated from the soil, with a minimum of R-10 insulation. The insulation shall be an approved product for its intended use. If a soil gas control system is present below the radiant slab, which results in increased convective flow below the radiant slab, the radiant slab shall be thermally isolated from the sub-slab gravel layer.


     502.1.4.10 Below Grade Walls: Below grade exterior wall insulation used on the exterior (cold) side of the wall shall extend from the top of the below grade wall to the top of the footing and shall be approved for below grade use. Above grade insulation shall be protected.


     Insulation used on the interior (warm) side of the wall shall extend from the top of the below grade wall to the below grade floor level.


     502.1.5 Glazing and Door U-factors: Glazing and door U-factors shall be determined in accordance with sections 502.1.5.1 and 502.1.5.2. All products shall be labeled with the NFRC certified or default U-factor. The labeled U-factor shall be used in all calculations to determine compliance with this Code. Sealed insulating glass shall conform to, or be in test for, ASTM E-774-81 class A.


EXCEPTIONS: 1. For glazed wall systems, assemblies with all of the following features are deemed to satisfy the vertical glazing U-factor requirement in ((Table 6-1 through 6-6)) Table 6-1 or 6-2 options with vertical glazing U-0.40 and greater:
a. Double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e=0.10 maximum, with 90% minimum argon gas fill, and a non-aluminum spacer (as defined in footnote 1 to Table 10-6B), and
b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum clad wood, vinyl, aluminum clad vinyl, or reinforced vinyl.
The only labeling requirement for products using this exception shall be a description of the product and a label stating: "This product is deemed to satisfy the ((Table 6-1 through 6-6)) Table 6-1 or 6-2 vertical glazing U-factor requirement using the exception to Section 502.1.5 in the Washington State Energy Code."
2. For overhead glazing, assemblies with all of the following features are deemed to satisfy the overhead glazing U-factor requirement in ((all Table 6-1 through 6-6)) Table 6-1 or 6-2 options except the unlimited glazing area options (((Option VIII in Table 6-2, Option IX in Table 6-4, and Option VIII for Climate Zone 1 and Option IX for Climate Zone 2 in Table 6-6))) (Option III in Table 6-1 and Option IV in Table 6-2):
a. Either, double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e=0.20 maximum, with 90% minimum argon gas fill, or, triple glazed plastic domes, and
b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum clad wood, vinyl, aluminum clad vinyl, or reinforced vinyl.
The only labeling requirement for products using this exception shall be a description of the product and a label stating: "This product is deemed to satisfy the ((Table 6-1 through 6-6)) Table 6-1 or 6-2 overhead glazing U-factor requirement using the exception to Section 502.1.5 in the Washington State Energy Code."
3. For solariums with a floor area which does not exceed 300 square feet, assemblies which comply with the features listed in exception 2 are deemed to satisfy the vertical glazing and overhead glazing U-factor requirement in ((Table 6-1 through 6-6)) Table 6-1 or 6-2 options with vertical glazing U-0.40 and greater.
The only labeling requirement for products using this exception shall be a description of the product and a label stating: "This product is deemed to satisfy the ((Table 6-1 through 6-6)) Table 6-1 or 6-2 vertical glazing and overhead glazing U-factor requirements using the exception to Section 502.1.5 in the Washington State Energy Code."

     502.1.5.1 Standard Procedure for Determination of Glazing U-factors: U-factors for glazing shall be determined, certified and labeled in accordance with the National Fenestration Rating Council (NFRC) Product Certification Program (PCP), as authorized by an independent certification and inspection agency licensed by the NFRC. Compliance shall be based on the Residential Model Size. Product samples used for U-factor determinations shall be production line units or representative of units as purchased by the consumer or contractor. Products that are listed in the NFRC Certified Products Directory or certified to the NFRC standard shall not use default values.

EXCEPTIONS: 1. Glazing products without NFRC ratings may be assigned default U-factors from Table 10-6A for vertical glazing and from Table 10-6E for overhead glazing.
2. Units without NFRC ratings produced by a small business may be assigned default U-factors from Table 10-6A for garden windows, from Table 10-6B for other vertical glazing, and from Table 10-6E for overhead glazing.

     502.1.5.2 Standard Procedure for Determination of Door U-factors: All doors, including fire doors, shall be assigned default U-factors from Table 10-6C.


EXCEPTIONS: 1. U-factors determined, certified and labeled in accordance with the National Fenestration Rating Council (NFRC) Product Certification Program (PCP), as authorized by an independent certification and inspection agency licensed by the NFRC.
2. The default values for the opaque portions of doors shall be those listed in Table 10-6C, provided that the U-factor listed for a door with a thermal break shall only be allowed if both the door and the frame have a thermal break.
3. One unlabeled or untested exterior swinging door with the maximum area of 24 square feet may be installed for ornamental, security or architectural purposes. Products using this exception shall not be included in ((either)) the U-factor ((or glazing area)) calculation requirements, however glazing area shall be included in glazing area calculations.

     502.1.6 Moisture Control:


     502.1.6.1 Vapor Retarders: Vapor retarders shall be installed on the warm side (in winter) of insulation as specified in the following cases.

EXCEPTION: Vapor retarder installed with not more than 1/3 of the nominal R-value between it and the conditioned space.

     502.1.6.2 Floors: Floors separating conditioned space from unconditioned space shall have a vapor retarder installed. The vapor retarder shall have a one perm dry cup rating or less (i.e., four mil [0.004 inch thick] polyethylene or kraft faced material).


     502.1.6.3 Roof/Ceilings: Roof/ceiling assemblies where the ventilation space above the insulation is less than an average of 12 inches shall be provided with a vapor retarder. Faced batt insulation where used as a vapor retarder shall be face stapled. Single rafter joist vaulted ceiling cavities shall be of sufficient depth to allow a minimum one inch vented air space above the insulation.


     502.1.6.4: Vapor retarders shall not be required in roof/ceiling assemblies where the ventilation space above the insulation averages 12 inches or greater.


     502.1.6.5: Vapor retarders shall not be required where all of the insulation is installed between the roof membrane and the structural roof deck.


     502.1.6.6 Walls: Walls separating conditioned space from unconditioned space shall have a vapor retarder installed. Faced batt insulation shall be face stapled.


     502.1.6.7 Ground Cover: A ground cover of six mil (0.006 inch thick) black polyethylene or approved equal shall be laid over the ground within crawl spaces. The ground cover shall be overlapped 12 inches minimum at the joints and shall extend to the foundation wall.

EXCEPTION: The ground cover may be omitted in crawl spaces if the crawl space has a concrete slab floor with a minimum thickness of 3-1/2 inches.

     502.2 Thermal Criteria for Group R Occupancy:


     502.2.1 UA Calculations: The proposed UA as calculated using Equations 2 and 3 shall not exceed the target UA as calculated using Equation 1. For the purpose of determining equivalent thermal performance, the glazing area for the target UA shall be calculated using values in Table 5-1. The opaque door area shall be the same in the target UA and the proposed UA.

EXCEPTION: Log and solid timber walls that have a minimum average thickness of 3.5" and with space heat type other than electric resistance, are exempt from wall target UA and proposed UA calculations.

     502.2.2 Space Heat Type: The following two categories comprise all space heating types:


     1. Electric Resistance: Space heating systems which include baseboard units, radiant units and forced air units as either the primary or secondary heating system.

EXCEPTION: Electric resistance systems for which the total electric heat capacity in each individual dwelling unit does not exceed the greater of: 1) One thousand watts (1000 w) per dwelling unit, or; 2) One watt per square foot (1 w/ft2) of the gross floor area.

     2. Other: All gas, wood, oil and propane space heating systems, unless electric resistance is used as a secondary heating system, and all heat pump space heating systems. (See EXCEPTIONS, Electric Resistance, section 502.2.2 above.)


     502.3 Reserved.


     502.4 Air Leakage:


     502.4.1 General: The requirements of this section shall apply to all buildings and structures, or portions thereof, and only to those locations separating outdoor ambient conditions from interior spaces that are heated or mechanically cooled.


     502.4.2 Doors and Windows, General: Exterior doors and windows shall be designed to limit air leakage into or from the building envelope. Site-constructed doors and windows shall be sealed in accordance with Section 502.4.3.


     502.4.3 Seals and Weatherstripping:


     a. Exterior joints around windows and door frames, openings between walls and foundation, between walls and roof and wall panels; openings at penetrations of utility services through walls, floors and roofs; and all other openings in the building envelope for all occupancies and all other openings in between units in R-1 occupancy shall be sealed, caulked, gasketed or weatherstripped to limit air leakage. Other exterior joints and seams shall be similarly treated, or taped, or covered with moisture vapor permeable housewrap.


     b. All exterior doors or doors serving as access to an enclosed unheated area shall be weatherstripped to limit leakage around their perimeter when in a closed position.


     c. Site built windows are exempt from testing but shall be made tight fitting. Fixed lights shall have glass retained by stops with sealant or caulking all around. Operating sash shall have weatherstripping working against overlapping trim and a closer/latch which will hold the sash closed. The window frame to framing crack shall be made tight with caulking, overlapping membrane or other approved technique.


     d. Openings that are required to be fire resistive are exempt from this section.


     502.4.4 Recessed Lighting Fixtures: When installed in the building envelope, recessed lighting fixtures shall meet one of the following requirements:


     1. Type IC rated, manufactured with no penetrations between the inside of the recessed fixture and ceiling cavity and sealed or gasketed to prevent air leakage into the unconditioned space.


     2. Type IC rated, installed inside a sealed box constructed from a minimum 1/2 inch thick gypsum wall board, or constructed from a preformed polymeric vapor barrier, or other air tight assembly manufactured for this purpose.


     3. Type IC rated, certified under ASTM E283 to have no more than 2.0 cfm air movement from the conditioned space to the ceiling cavity. The lighting fixture shall be tested at 75 Pascals or 1.57 lbs/ft2 pressure difference and have a label attached, showing compliance.

[Statutory Authority: RCW 19.27A.025, 19.27A.045. 01-03-010, § 51-11-0502, filed 1/5/01, effective 7/1/01; 98-03-003, § 51-11-0502, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, § 51-11-0502, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, § 51-11-0502, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0502, filed 12/19/91, effective 7/1/92. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, § 51-11-0502, filed 12/19/90, effective 7/1/91.]

     Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION(Amending WSR 01-03-010, filed 1/5/01, effective 7/1/01)

WAC 51-11-0503   Building mechanical systems.  

     503.1 General: This section covers the determination of design requirements, system and component performance, control requirements, insulating systems and duct construction.


     503.2 Calculations of Heating and Cooling Loads, and System Sizing Limits: The design parameters specified in Chapter 3 shall apply for all computations.


     503.2.1 Calculation Procedures: Heating and cooling design loads for the purpose of sizing HVAC systems are required and shall be calculated in accordance with accepted engineering practice, including infiltration and ventilation.


     503.2.2 Space Heating and Space Cooling System Sizing Limits: Building mechanical systems for all buildings which provide space heating and/or space cooling shall be sized no greater than two hundred percent (200%) of the heating and cooling design loads as calculated above.


EXCEPTIONS: The following limited exemptions from the sizing limit shall be allowed; however, in all cases heating and/or cooling design load calculations shall be submitted.
1. For equipment which provides both heating and cooling in one package unit, including heat pumps with electric heating and cooling and gas-pack units with gas heating and electric cooling, compliance need only be demonstrated for either the space heating or space cooling system size.
2. Natural gas- or oil-fired space heating equipment whose total rated space heating output in any one dwelling unit is
a. 40,000 Btu/h or less is exempt from the sizing limit,
b. larger than 40,000 Btu/h may exceed the two hundred (200%) percent sizing limit provided that the installed equipment has an annual fuel utilization efficiency (AFUE) of not less than ninety (90%) percent.
3. Stand-by equipment may be installed if controls and other devices are provided which allow redundant equipment to operate only when the primary equipment is not operating.

     503.3 Simultaneous Heating and Cooling: Systems and equipment that provide simultaneous heating and cooling shall comply with the requirements in, as appropriate, Section 1422 or Section 1435.


     503.4 HVAC Equipment Performance Requirements: All heating equipment shall meet the requirements of the 1987 National Appliance Energy Conservation Act (NAECA) and be so labeled. Equipment shall also comply with Section 1411.


     ((503.4.1 Equipment Components:


     503.4.1.1: The requirements of this section apply to equipment and mechanical component performance for heating, ventilating and air-conditioning systems. Equipment efficiency levels are specified. Data furnished by the equipment supplier or certified under a nationally recognized certification program or rating procedure shall be used to satisfy these requirements. Equipment efficiencies shall be based on the standard rating conditions in Tables 5-4, 5-5 or 5-6 as appropriate.


     503.4.1.2: Where components from more than one manufacturer are assembled into systems regulated under this section, compliance for each component shall be as specified in sections 503.4.2 through 503.4.6 of this Code.


     503.4.2: HVAC System Heating Equipment Heat Pump-heating Mode. Heat pumps whose energy input is entirely electric shall have a coefficient of performance (COP) heating, not less than the values in Table 5-7. Heat Pumps with supplementary backup heat other than electricity shall meet the requirements of Table 5-7.


     503.4.2.1: These requirements apply to, but are not limited to, unitary (central) heat pumps (air source and water source) in the heating mode, water source (hydronic) heat pumps as used in multiple-unit hydronic HVAC systems, and heat pumps in the packaged terminal air-conditioner in the heating mode.


     503.4.2.3 Supplementary Heater: The heat pump shall be installed with a control to prevent supplementary backup heater operation when the operating load can be met by the heat pump compression cycle alone.


     503.4.2.4 Heat Pump Controls: Requirements for heat pump controls are listed in section 503.8.3.5 of this Code.


     503.4.3 HVAC System Combustion Equipment: For Group R Occupancy, all gas, oil, and propane central heating systems shall have a minimum AFUE of 0.78*. All other Group R Occupancy heating equipment fueled by gas, oil, or propane shall be equipped with an intermittent ignition device, or shall comply with the efficiencies as required in the 1987 National Appliances Energy Conservation Act (Public Law 100-12).


     *HVAC Heating system efficiency trade-offs shall be made using Chapters 4 or 6 of this Code.


     503.4.4 Packaged and Unitary HVAC System Equipment, Electrically Operated, Cooling Mode: HVAC system equipment as listed below, whose energy input in the cooling mode is entirely electric, shall have an energy efficiency ratio (EER) or a seasonal energy efficiency ratio (SEER) cooling not less than values in Table 5-8.


     503.4.4.1: These requirements apply to, but are not limited to, unitary (central) and packaged terminal heat pumps (air source and water source); packaged terminal air conditioners.


     503.4.5 Other HVAC Equipment: HVAC equipment, other than that addressed in Sections 503.4.2 through 503.4.4, shall have a minimum performance at the specified rating conditions not less than the values shown in Tables 14-1 through 14-3.
))


     503.5 Reserved.


     503.6 Balancing: The HVAC system design shall provide a means for balancing air and water systems. Balancing the system shall include, but not be limited to, dampers, temperature and pressure test connections and balancing valves.


     503.7 Cooling with Outdoor Air (Economizer Cycle): Systems and equipment that provide mechanical cooling shall comply with Section 1413 and, as appropriate, Section 1423 or 1433.


     503.8 Controls:


     503.8.1 Temperature Control: Each system shall be provided with at least one adjustable thermostat for the regulation of temperature. Each thermostat shall be capable of being set by adjustment or selection of sensors as follows:


     503.8.1.1: When used to control heating only: Fifty-five degrees to seventy-five degrees F.


     503.8.1.2: When used to control cooling only: Seventy degrees to eighty-five degrees F.


     503.8.1.3: When used to control both heating and cooling, it shall be capable of being set from fifty-five degrees to eighty-five degrees F and shall be capable of operating the system heating and cooling in sequence. The thermostat and/or control system shall have an adjustable deadband of not less than ten degrees F.


     503.8.2 Humidity Control: If a system is equipped with a means for adding moisture to maintain specific selected relative humidities in space or zones, a humidistat shall be provided. Humidistats shall be capable of being set to prevent new energy from being used to produce space-relative humidity above thirty percent.


EXCEPTION: Special uses requiring different relative humidities may be permitted when approved by the building official.

     503.8.3 Zoning for Temperature Control:


     503.8.3.1 One- and Two-Family Dwellings: At least one thermostat for regulation of space temperature shall be provided for each separate system. In addition, a readily accessible manual or automatic means shall be provided to partially restrict or shut off the heating and/or cooling input to each zone or floor.


     503.8.3.2 Multifamily Dwellings: For multifamily dwellings, each individual dwelling unit shall have at least one thermostat for regulation of space temperature. A readily accessible manual or automatic means shall be provided to partially restrict or shut off the heating and/or cooling input to each room. Spaces other than living units shall meet the requirements of 503.8.3.3.


     503.8.3.3 Reserved.


     503.8.3.4 Control Setback and Shut-off:


     Residential Occupancy Groups. One- and Two-Family and Multifamily dwellings -- The thermostat required in section 503.8.3.1 or section 503.8.3.2, or an alternate means such as a switch or clock, shall provide a readily accessible, manual or automatic means for reducing the energy required for heating and cooling during the periods of non-use or reduced need, such as, but not limited to unoccupied periods and sleeping hours. Lowering thermostat set points to reduce energy consumption of heating systems shall not cause energy to be expended to reach the reduced setting.


     503.8.3.5 Heat Pump Controls: Programmable thermostats are required for all heat pump systems. The cut-on temperature for the compression heating shall be higher than the cut-on temperature for the supplementary heat, and the cut-off temperature for the compression heating shall be higher than the cut-off temperature for the supplementary heat. Heat pump thermostats will be capable of providing at least two programmable setback periods per day. The automatic setback thermostat shall have the capability of limiting the use of supplemental heat during the warm-up period.


     503.9 Air Handling Duct System Insulation: Ducts, plenums and enclosures installed in or on buildings shall be thermally insulated per Table 5-11.


EXCEPTIONS: Duct insulation (except where required to prevent condensation) is not required in any of the following cases:
1. When the heat gain or loss of the ducts, without      insulation, will not increase the energy requirements of the building.
2. Within the HVAC equipment.
3. Exhaust air ducts.
4. Supply or return air ducts installed in unvented crawl spaces with insulated walls, basements, or cellars in one-and two-family dwellings.

     503.10 Duct Construction: All duct work shall be constructed in accordance with Standards RS-15, RS-16, RS-17, RS-18, RS-19 or RS-20, as applicable, and the Uniform Mechanical Code.


     503.10.1 Leakage Testing: High-pressure and medium-pressure ducts shall be leak tested in accordance with the applicable standards in Chapter 7 of this Code with the rate of air leakage not to exceed the maximum rate specified in that standard.


     503.10.2 Seams and Joints: All low-pressure supply and return, including enclosed stud bays or joist cavities/space used to transport air, shall be securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic-plus-embedded-fabric systems or tapes installed in accordance with the manufacturer's installation instructions. Tapes and mastics used with rigid fibrous glass ducts shall be listed and labeled in accordance with UL 181A. Tapes and mastics used with flexible air ducts shall be listed and labeled in accordance with UL 181B. Duct tape is not permitted as a sealant on any ducts.


EXCEPTION: Ducts or building cavities used for air distribution that are located entirely within the conditioned space of the building are exempt from this section.

     503.10.3 Dampers: Requirements for Automatic or manual dampers are found in the Washington State Ventilation and Indoor Air Quality Code.


     503.10.4 Duct Insulation: Ducts shall meet the insulation requirements specified in Table 5-11.


     503.11 Pipe Insulation: All piping shall be thermally insulated in accordance with Table 5-12.


EXCEPTION: Piping installed within unitary HVAC equipment.

Cold water pipes outside the conditioned space shall be insulated in accordance with the Washington State Plumbing Code (chapter 51-46 WAC).

[Statutory Authority: RCW 19.27A.025, 19.27A.045. 01-03-010, § 51-11-0503, filed 1/5/01, effective 7/1/01. Statutory Authority: RCW 19.27A.020, 19.27A.045, and 19.27.020. 98-24-075, § 51-11-0503, filed 12/1/98, effective 7/1/99. Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, § 51-11-0503, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, § 51-11-0503, filed 10/18/93, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0503, filed 12/19/91, effective 7/1/92. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, § 51-11-0503, filed 12/19/90, effective 7/1/91.]


AMENDATORY SECTION(Amending WSR 01-03-010, filed 1/5/01, effective 7/1/01)

WAC 51-11-0530   Table 5-1.  

TABLE 5-1

TARGET COMPONENT VALUES FOR GROUP R OCCUPANCY

((Electric Resistance)) ((Other Fuels
Climate Zone Climate Zone
Component 1 2 1 2
Glazing % Floor Area 15% 15% 15% 15%
Vertical Glazing U-Factor U = 0.400 U = 0.400 U = 0.650 U = 0.600
Overhead Glazing U-Factor U = 0. 58 U = 0. 58 U = 0. 68 U = 0.64
Doors U = 0.200

(R-5)

U = 0.200

(R-5)

U = 0.400

(R-2.5)

U = 0.400

(R-2.5)

Ceilings

     Attic

     Single Rafter/

     Joist Vaulted

U = 0.031

(R-38)

U = 0.034

(R-30)

U = 0.031

(R-38)

U = 0.034

(R-30)

U = 0.036

(R-30)

U = 0.034

(R-30)

U = 0.031

(R-38)

U = 0.034

(R-30)

Walls2

     Space Heat Type:

     Electric Resistance

U = 0.058

(R-19A)

U = 0.044

(((R-19+5A))) (R-19A + R-5)

U = 0.0621

(R-19)

U = 0.0621

(R-19)

     Other U = 0.0621

(R-19)

U = 0.0621

(R-19)

Floors U = 0.029

(R-30)

U = 0.029

(R-30)

U = 0.041

(R-19)

U = 0.029

(R-30)

Slab on Grade

     Slab R-Value

F = 0.54

(R-10)

F = 0.54

(R-10)

F = 0.54

(R-10)

F = 0.54

(R-10)

Below Grade Interior
Wall R-Value R-19 R-19 R-19 R-19
2' Depth: Walls

     Slab

U = 0.043

F = 0.69

U = 0.043

F = 0.69

U = 0.043

F = 0.69

U = 0.043

F = 0.69

3.5' Depth: Walls

     Slab

U = 0.041

F = 0.64

U = 0.041

F = 0.64

U = 0.041

F = 0.64

U = 0.041

F = 0.64

7' Depth: Walls

     Slab

U = 0.037

F = 0.57

U = 0.037

F = 0.57

U = 0.037

F = 0.57

U = 0.037

F = 0.57

Below Grade Exterior
Wall R-Value R-10 R-12 R-10 R-12
2' Depth: Walls

     Slab

U = 0.070

F = 0.60

U = 0.061

F = 0.60

U = 0.070

F = 0.60

U = 0.061

F = 0.60

3.5' Depth: Walls

     Slab

U = 0.064

F = 0.57

U = 0.057

F = 0.57

U = 0.064

F = 0.57

U = 0.057

F = 0.57

7' Depth: Walls

     Slab

U = 0.056

F = 0.42

U = 0.050

F = 0.42

U = 0.056

F = 0.42

U = 0.050

F = 0.42))


1. Log and Solid Timber walls that have a minimum average thickness of 3.5" are exempt from wall target UA and proposed UA calculations.

2. "A" means advanced framing. For more information, see Section 1005.2.

[Statutory Authority: RCW 19.27A.025, 19.27A.045. 01-03-010, § 51-11-0530, filed 1/5/01, effective 7/1/01; 98-03-003, § 51-11-0530, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, § 51-11-0530, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0530, filed 12/19/91, effective 7/1/92.]


AMENDATORY SECTION(Amending WSR 92-01-140, filed 12/19/91, effective 7/1/92)

WAC 51-11-0533   Table 5-4 -- Reserved.  

((HVAC SYSTEM HEATING EQUIPMENT (HEAT PUMPS)

ELECTRICALLY OPERATED STANDARD RATING CONDITIONS



TYPE

CONDITIONS

AIR SOURCE

WATER SOURCE

Air entering equipment

Outdoor unit ambient

Entering water temp.

Water flow rate


°F

°F

°F


70°F (dry bulb)

47°F (dry bulb)

/43°F (wet bulb)

- - - - - - - - - - - -

- - - - - - - - - - - -


70°F (dry bulb)

17°F (dry bulb)

/15°F (wet bulb)

- - - - - - - - - - - -

- - - - - - - - - - - -


70°F (dry bulb)

- - - - - - - - - - - -

60°F

As used in cooling


((Standard ratings are at sea level.))

[Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0533, filed 12/19/91, effective 7/1/92.]


AMENDATORY SECTION(Amending WSR 92-01-140, filed 12/19/91, effective 7/1/92)

WAC 51-11-0534   Table 5-5 -- Reserved.  

((HVAC SYSTEM EQUIPMENT, ELECTRICALLY DRIVEN

STANDARD RATING CONDITIONS--COOLING

TEMPERATURES

DRY BULB

WET BULB

INLET

OUTLET
Air entering equipment

Condenser ambient

     (air cooled)

Condenser water

     (water cooled)

°F

°F

°F

80°

95°

----

67°

75°

----

----

----

85°

----

----

95°


Standard ratings are at sea level.))

[Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0534, filed 12/19/91, effective 7/1/92.]


AMENDATORY SECTION(Amending WSR 92-01-140, filed 12/19/91, effective 7/1/92)

WAC 51-11-0535   Table 5-6 -- Reserved.  

((APPLIED HVAC SYSTEM COMPONENTS ELECTRICALLY DRIVEN

STANDARD RATING CONDITIONS -- COOLING

ITEM CENTRIFUGAL OR SELF-CONTAINED

RECIPROCATING WATER CHILLER

CONDENSERLESS

RECIPROCATING

WATER-CHILLER


((Water Temperature,
°F
     Leaving chilled 44° 44°
     Entering chilled 54° 54°
     Leaving condenser 95° --
     Entering 85° --
Fouling Factor, Water
     Nonferrous tubes 0.0005* 0.0005
     Steel tubes 0.0010* 0.0010
     Refrigerant 0.0000* 0.0000
Condenser Ambient

     (air/evap. cooled)

°F 95°F (dry bulb)

/75°F (wet bulb)

--
Compressor saturated

discharge temperature

     Water cooled

     (evap. cooled)

°F -- 105°
     Air cooled

°F -- 120°

Standard ratings at sea level.
* hr• ft2• °F/Btu))

[Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0535, filed 12/19/91, effective 7/1/92.]


AMENDATORY SECTION(Amending WSR 92-01-140, filed 12/19/91, effective 7/1/92)

WAC 51-11-0536   Table 5-7 -- Reserved.  

((MINIMUM HEAT PUMP EFFICIENCIES, HEATING MODE1

SOURCE MINIMUM COP MINIMUM HSPF
Air Source:
     Split System 3.02 6.8
     Single Package System 3.02 6.6
Water Source 3.83 --
Ground Source 3.04 --
1 When tested at the standard rating specified in

     Table 5-4.

2 When tested @ 47°F (dry bulb)/43°F (wet bulb)
3 @ 70°F entering
4 @ 50°F entering))

[Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0536, filed 12/19/91, effective 7/1/92.]


AMENDATORY SECTION(Amending WSR 92-01-140, filed 12/19/91, effective 7/1/92)

WAC 51-11-0537   Table 5-8 -- Reserved.  

((MINIMUM EFFICIENCY FOR ELECTRIC HVAC EQUIPMENT, COOLING

AIR

COOLED

EVAP/

WATER

COOLED

STANDARD

RATING CAPACITY

SEER EER EER

Under 65,000 Btu/hr.

     ( 19,050 watts )

A. Split System 10.0 -- --
B. Single Package3 9.7 -- 9.31

65,000 Btu/hr. and over
---- 8.92 10.51
1 @ 80°F dry bulb / 67°F wet bulb
2 @ 95°F dry bulb
3 Prior to January 1, 1993 a minimum value of 8.0 SEER may be used.))

[Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0537, filed 12/19/91, effective 7/1/92.]


AMENDATORY SECTION(Amending WSR 01-03-010, filed 1/5/01, effective 7/1/01)

WAC 51-11-0601   Scope.  


     601.1 General: This chapter establishes design criteria in terms of prescribed requirements for building construction.


     The provisions of this chapter are applicable to all Group R Occupancies. Occupancies shall comply with all the requirements of Chapter 5 except for the modifications herein specified.


     For wood frame assemblies, the building envelope requirements of this chapter may be met by installing one of the prescriptive packages in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2. Installed components shall meet the requirements of section 602. Compliance with nominal R-Values shall be demonstrated for the thermal resistance of the added insulation in framing cavities and/or insulated sheathing only and shall not include the thermal transmittance of other building materials or air films, but shall permit interruption by occasional framing members. Other than wood frame assemblies with continuous insulation uninterrupted by framing shall also be allowed to comply with nominal R-values.


     For metal frame assemblies, compliance shall be demonstrated in accordance with Chapter 4 or Chapter 5 based on the assemblies in Chapter 10. Compliance with nominal R-values is not allowed, unless the full nominal R-value of the insulation is installed either inside or outside of the framing and is uninterrupted by framing.

[Statutory Authority: RCW 19.27A.025, 19.27A.045. 01-03-010, § 51-11-0601, filed 1/5/01, effective 7/1/01. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, § 51-11-0601, filed 2/10/94, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, § 51-11-0601, filed 12/19/90, effective 7/1/91.]


AMENDATORY SECTION(Amending WSR 98-03-003, filed 1/8/98, effective 7/1/98)

WAC 51-11-0602   Building envelope requirements for Group R Occupancy.  


     602.1 Roof/Ceiling: Ceilings below vented attics and single-rafter, joist-vaulted ceilings shall be insulated to not less than the nominal R-value specified for ceilings in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2 as applicable.


     602.2 Exterior Walls Both Above and Below Grade: Above grade exterior walls shall be insulated to not less than the nominal R-value specified in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2 as applicable. The following walls should be considered to meet ((R-19)) R-21 without additional documentation:


     1. 2 x 6 framed and insulated with ((R-19)) R-21 fiberglass batts.


     2. 2 x 4 framed and insulated with ((R-13)) R-15 fiberglass batts plus ((R-3.2)) R-4.0 foam sheathing.


     3. 2 x 4 framed and insulated with ((R-11)) R-13 fiberglass batts plus R-5.0 foam sheathing.


     602.3 Exterior Walls (Below Grade): Below grade exterior walls surrounding conditioned space shall be insulated to not less than the nominal R-value specified for below grade walls in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2 as applicable.


     602.4 Slab-on-grade Floors: Slab-on-grade floors shall be insulated along their perimeter to not less than the nominal R-values specified for slab-on-grade floors in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2 as applicable. Slab insulation shall be installed in compliance with section 502.1.4.8. See Chapter 5, section 502.1.4.9, for additional requirements for radiant slab heating.


     602.5 Floors Over Unconditioned Space: Floors over unconditioned spaces, such as vented crawl spaces, unconditioned basements, and parking garages shall be insulated to not less than the nominal R-value shown for floors over unconditioned spaces, in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2.


     602.6 Exterior Doors: Doors shall comply with Sections 602.6.1 and 602.6.2.


EXCEPTIONS: 1. Doors whose area and U-factor are included in the calculations for compliance with the requirements for glazing in section 602.7 shall be exempt from the door U-factor requirements prescribed in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2.
2. One unlabeled or untested exterior swinging door with the maximum area of 24 square feet may be installed for ornamental, security or architectural purposes. Products using this exception shall not be included in either the U-factor or glazing area calculation requirements.
     602.6.1 Exterior Door Area: For half-lite and full-lite doors, the glazing area shall be included in calculating the allowed total glazing area in Section 602.7.1. Single glazing used for ornamental, security or architectural purposes shall be calculated using the exception to Section 602.7.2.


     602.6.2 Exterior Door U-Factor: Doors, including fire doors, shall have a maximum area weighted average U-factor not exceeding that prescribed in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2.


     602.7 Glazing:


     602.7.1 Glazing Area: The total glazing area as defined in Chapter 2 shall not exceed the percentage of gross conditioned floor area specified in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2. This area shall also include any glazing in doors.


     602.7.2 Glazing U-Factor: The total glazing area as defined in Chapter 2 shall have an area weighted average U-factor not to exceed that specified in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2. U-factors for glazing shall be determined in accordance with section 502.1.5. These areas and U-factors shall also include any doors using the exception of section 602.6.


     If the U-factors for all vertical and overhead glazing products are below the appropriate U-factor specified, then no calculations are required. If compliance is to be achieved through an area weighted calculation, then the areas and U-factors shall be included in the plans submitted with a building permit application.


EXCEPTION: Single glazing for ornamental, security, or architectural purposes and double glazed garden windows with a wood or vinyl frame shall be exempt from the U-factor calculations but shall have its area ((doubled)) tripled and shall be included in the percentage of the total glazing area as allowed for in ((Tables 6-1 to 6-6)) Table 6-1 or 6-2. The maximum area (before ((doubling)) tripling) allowed for the total of all single glazing and garden windows is one percent of the floor area.

     602.8 Air Leakage For Group R Occupancy: The minimum air leakage control measures shall be as specified in section 502.4 as applicable.

[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, § 51-11-0602, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, § 51-11-0602, filed 2/10/94, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, § 51-11-0602, filed 12/19/90, effective 7/1/91.]


AMENDATORY SECTION(Amending WSR 94-05-059, filed 2/10/94, effective 4/1/94)

WAC 51-11-0603   Building mechanical systems for Group R Occupancy.  


     603.1: Group R Occupancies that are space heated by air-to-air, ground-to-air, or water-to-air heat pumps shall comply with ((Table 6-2 or 6-4 or 6-6 for other fuels)) Table 6-1 or 6-2. System sizing shall be determined by an analysis consistent with section 503.2 of this Code, or, when approved by the building official, Chapter 9. All mechanical equipment efficiencies and service water heating system efficiencies shall comply with standards as stated in sections 503 and 504 of this Code.

[Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, § 51-11-0603, filed 2/10/94, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, § 51-11-0603, filed 12/19/90, effective 7/1/91.]


AMENDATORY SECTION(Amending WSR 01-03-010, filed 1/5/01, effective 7/1/01)

WAC 51-11-0625   Table 6-1.  

((TABLE 6-1

PRESCRIPTIVE REQUIREMENTS1 **FOR GROUP R OCCUPANCY

CLIMATE ZONE 1 • HEATING BY ELECTRIC RESISTANCE

Option Glazing Area10:

% of

Floor

Glazing U-Factor Door 9

U-

Factor

Ceiling2 Vaulted Ceiling3 Wall Above Grade Wall• int4 Below Grade Wall• ext4 Below Grade Floor5 Slab4

on

Grade

Vertical Overhead11
I. 10% 0.46 0. 58 0.40 R-38 R-30 R-21 R-21 R-10 R-30 R-10
II. 12% 0.43 0. 58 0.20 R-38 R-30 R-19 R-19 R-10 R-30 R-10
III. 12% 0.40 0. 58 0.40 R-38 R-30 R-21 R-21 R-10 R-30 R-10
IV.* 15% 0.40 0. 58 0.20 R-38 R-30 R-19 R-19 R-10 R-30 R-10
V. 18% 0.39 0. 58 0.20 R-38 R-30 R-21 R-21 R-10 R-30 R-10
VI. 21% 0.36 0. 58 0.20 R-38 R-30 R-21 R-21 R-10 R-30 R-10
VII.7 25% 0.327 0. 58 0.20 R-38 R-30 R-19

+R-58

R-21 R-10 R-30 R-10
VIII.7 30% 0.297 0. 58 0.20 R-38 R-30 R-19

+R-58

R-21 R-10 R-30 R-10

* Reference Case
** Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1.
1. Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 19%, it shall comply with all of the requirements of the 21% glazing option (or higher). Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code.
2. Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling.
3. Requirement applicable only to single rafter or joist vaulted ceilings.
4. Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2.
5. Floors over crawl spaces or exposed to ambient air conditions.
6. Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4.
7. The following options shall be applicable to buildings less than three stories: 0.35 maximum for glazing areas of 25% or less; 0.32 maximum for glazing areas of 30% or less.
8. This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing.
9. Doors, including all fire doors, shall be assigned default U-factors from Table 10-6C.
10. Where a maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U-factor of U=0.040 or less is not included in glazing area limitations.
11. Overhead glazing shall have U-factors determined in accordance with NFRC 100 or as specified in Section 502.1.5.))

TABLE 6-1

PRESCRIPTIVE REQUIREMENTS0,1 FOR GROUP R OCCUPANCY

CLIMATE ZONE 1

Option Glazing Area10:

% of

Floor

Glazing U-Factor Door9

U-

Factor

Ceiling2 Vaulted Ceiling3 Wall12 Above Grade Wall• int4 Below Grade Wall• ext4 Below Grade Floor5 Slab6

on

Grade

Vertical Overhead11
I. 12% 0.35 0.58 0.20 R-38 R-30 R-15 R-15 R-10 R-30 R-10
II.* 15% 0.40 0.58 0.20 R-38 R-30 R-21 R-21 R-10 R-30 R-10
III. Unlimited Group R-3 Occupancy only 0.40 0.58 0.20 R-38 R-30 R-21 R-21 R-10 R-30 R-10

* Reference Case

TABLE 6-2

PRESCRIPTIVE REQUIREMENTS0,1 FOR GROUP R OCCUPANCY

CLIMATE ZONE 2

Option Glazing Area10:

% of

Floor

Glazing U-Factor Door9

U-

Factor

Ceiling2 Vaulted Ceiling3 Wall12 Above Grade Wall• int4 Below Grade Wall• ext4 Below Grade Floor5 Slab6

on

Grade

Vertical Overhead11
I. 10% 0.40 0.58 0.20 R-38 R-30 R-21 Int7 R-21 R-12 R-30 R-10
II.* 15% 0.40 0.58 0.20 R-38 R-30 R-19 +R-58 R-21 R-12 R-30 R-10
III. 17% 0.37 0.58 0.20 R-38 R-30 R-19 +R-58 R-21 R-12 R-30 R-10
IV. Unlimited Group R-3 Occupancy only 0.35 0.58 0.20 R-38 R-30 R-21 Int7 R-21 R-12 R-30 R-10

* Reference Case
0. Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1.
1. Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 13%, it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code.
2. Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling.
3. Requirement applicable only to single rafter or joist vaulted ceilings.
4. Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2.
5. Floors over crawl spaces or exposed to ambient air conditions.
6. Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4.
7. Int. denotes standard framing 16 inches on center with headers insulated with a minimum of R-5 insulation.
8. This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing.
9.