WSR 01-02-098

PERMANENT RULES

BUILDING CODE COUNCIL


[ Filed January 3, 2001, 11:40 a.m. , effective July 1, 2001 ]

Date of Adoption: November 17, 2000.

Purpose: To make changes to the Washington state amendments to the 1997 Uniform Mechanical Code, chapter 51-42 WAC.

Citation of Existing Rules Affected by this Order: Amending chapter 51-42 WAC, Sections 405, 1103, 1105, 1109, 1110, 1111, 1112, 1113, 1114, 1115, 1116, 1117, 1118, 1119, 1120, 1121, 1122, 1123, 1124, 1126, 1301.

Statutory Authority for Adoption: RCW 19.27.031, 19.27.074.

Adopted under notice filed as WSR 00-16-130 on August 2, 2000.

Changes Other than Editing from Proposed to Adopted Version: The proposed amendments to the following sections were not adopted: 1101.

Number of Sections Adopted in Order to Comply with Federal Statute: New 0, Amended 0, Repealed 0; Federal Rules or Standards: New 0, Amended 0, Repealed 0; or Recently Enacted State Statutes: New 0, Amended 0, Repealed 0.

Number of Sections Adopted at Request of a Nongovernmental Entity: New 18, Amended 3, Repealed 0.

Number of Sections Adopted on the Agency's Own Initiative: New 0, Amended 0, Repealed 0.

Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, Amended 0, Repealed 0.

Number of Sections Adopted Using Negotiated Rule Making: New 0, Amended 0, Repealed 0; Pilot Rule Making: New 0, Amended 0, Repealed 0; or Other Alternative Rule Making: New 18, Amended 3, Repealed 0. Effective Date of Rule: July 1, 2001.

January 3, 2001

Tim Nogler

for Jim Lewis

Council Vice Chair

OTS-4187.3


NEW SECTION
WAC 51-42-0405   Section 405 -- Direct gas-fired make-up air systems.  


405.1 General. Direct gas-fired make-up air heaters shall not be installed for comfort heating in other than Group F, S, or U Occupancies.


EXCEPTION: Direct gas-fired make-up air heaters may be installed in accordance with Section 909.

[]


AMENDATORY SECTION(Amending WSR 98-02-056, filed 1/6/98, effective 7/1/98)

WAC 51-42-1103   Refrigeration system classification.  


1103.1 General. For the purposes of applying Tables 1104.1, 1104.2(1), and 1104.2(2), refrigeration systems shall be classified as high-probability or low-probability system based on the potential hazard resulting from a leakage of refrigerant into an occupancy-classified area other than the machinery room.


1103.2 High-probability systems. Direct systems and indirect open-spray systems shall be classified as high-probability systems.


EXCEPTION: An indirect open-spray system shall not be required to be classified as a high-probability system if the pressure of the secondary coolant is at all times (operating and standby) greater than the pressure of the refrigerant.

1103.3 Low-probability((V)) systems. Double-indirect open-spray systems, indirect closed systems and indirect-vented closed systems shall be classified as low-probability systems, provided that all refrigerant-containing piping and fittings are isolated when the quantities in Table 1104.1 are exceeded.

[Statutory Authority: RCW 19.27.031 and 19.27.074. 98-02-056, 51-42-1103, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-056, filed 1/6/98, effective 7/1/98)

WAC 51-42-1105   Machinery room, general requirements.  


1105.1 General. Where required by Table 1104.2(1), a machinery room shall be provided to enclose refrigeration systems located indoors. Access to the machinery room shall be restricted to authorized personnel. For rooms where occupational exposure could occur, see WAC 296-62-07515 and 296-62-3112.


1105.2 Dimensions. A machinery room shall be dimensioned so as to provide clearances required by Chapter 3. There shall be clear head room of not less than 7 feet 3 inches (2210 mm) below equipment located over passageways.


1105.3 Doors. Each machinery room shall have self-closing, weather-stripped doors opening in the direction of egress travel. Doors and door openings shall comply with the requirements of the Building Code.


1105.4 Openings.
Openings to other parts of the building that permit passage of escaping refrigerant to other parts of the building are prohibited. Ducts and air handlers in the machinery room that operate at a lower pressure than the room shall be sealed to prevent any refrigerant leakage from entering the airstream.


EXCEPTIONS: 1. Egress doors serving the machinery room.
2. Access doors and panels in air ducts and air-handling units, provided that such openings are gasketed and tight fitting.
1105.5 Refrigerant vapor detector. Machinery rooms shall contain a refrigerant vapor detector with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant vapor from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values shown in Table 1104.1. Detectors and alarms shall be placed in approved locations. Detection and alarm systems shall be powered and supervised, monitored and annunciated, and installed and maintained as required by Section 6313 of the Fire Code.


EXCEPTION: Detectors are not required for ammonia systems complying with Section 1106.8.

1105.6 Tests. Periodic tests of the detector, alarm and mechanical ventilating system shall be performed in accordance with manufacturer's specifications and as required by the code official.


1105.7 Fuel-burning equipment. Open flames that use combustion air from the machinery room shall not be installed in a machinery room.


EXCEPTIONS: 1. Matches, lighters, halide leak detectors and similar devices.
2. Where the refrigerant is carbon dioxide or water.
3. Fuel-burning equipment shall not be prohibited in the same machinery room with refrigerant-containing equipment where combustion air is ducted from outside the machinery room and sealed in such a manner as to prevent any refrigerant leakage from entering the combustion chamber, or where a refrigerant vapor detector is employed to automatically shut off the combustion process in the event of refrigerant leakage.
1105.8 Sign. A sign shall be posted on the machinery room door prohibiting access of unauthorized personnel.


1105.9 Ventilation. Machinery rooms shall be mechanically ventilated to the outdoors. Mechanical ventilation shall be capable of exhausting the minimum quantity of air both at the normal operating and emergency conditions. Multiple fans or multispeed fans shall be allowed in order to produce the emergency ventilation rate and to obtain a reduced airflow for normal ventilation. Fans providing refrigeration machinery room temperature control or automatic response to refrigerant vapor are allowed to be automatically controlled to provide intermittent ventilation as conditions require.


EXCEPTION: Where a refrigerating system is located outdoors more than 20 feet (6096 mm) from any building opening and is enclosed by a penthouse, lean-to or other open structure, natural or mechanical ventilation shall be provided. Location of the openings shall be based on the relative density of the refrigerant to air. The free-aperture cross section for the ventilation of the machinery room shall be not less than:

((Q = 100 x √G
For SI: Q = 0.07 x √G))

F = √G
For SI: F = 0.138 √G


where:


F = The free opening area in square feet (m2).


G = The mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room.


1105.9.1 Discharge location. The discharge of the air shall be to the outdoors in accordance with Chapter 5. Exhaust from mechanical ventilation systems shall be discharged not less than 20 feet (6096 mm) from a property line or openings into buildings.


1105.9.2 Supply air. Provisions shall be made for supply air to replace that being exhausted. Openings for supply air shall be located to avoid intake of exhaust air. Air supply and exhaust ducts to the machinery room shall serve no other area, shall be constructed in accordance with Chapter 5 and shall be covered with corrosion-resistant screen of not less than 1/4 inch (6.4 mm) mesh. The supply air shall be taken from directly outside the building. Intakes shall be fitted with backdraft dampers or similar approved flow control means to prevent reverse flow.


1105.9.3 Quantity--normal ventilation. During occupied conditions the mechanical ventilation system shall exhaust the larger of the following:


1. Not less than 0.5 cfm per square foot (0.0025 m3/s m2) of machinery room area or 20 cfm (0.009 m3/s) per person; or


2. A volume required to maintain a maximum temperature rise of 18F (-7.8C) based on all of the heat-producing machinery in the room.


1105.9.4 Quantity--emergency conditions. Upon actuation of the refrigerant detector required in Section 1105.5, the mechanical ventilation system shall exhaust air from the machinery room in the following quantity:


((F = √G
For SI: F = 0.138 √G))

Q = 100 x √G
For SI: Q = 0.07 x √G


where:


Q = The airflow in cubic feet per minute (m3/s).


G = The design mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room.


1105.10 Termination of relief devices. In the equipment room, pressure relief devices, fusible plugs and purge systems shall terminate outside of the structure at a location not less than 15 feet (4572 mm) above the adjoining grade level and not less than 20 feet (6096 mm) from any window, ventilation opening or exit.

[Statutory Authority: RCW 19.27.031 and 19.27.074. 98-02-056, 51-42-1105, filed 1/6/98, effective 7/1/98.]


NEW SECTION
WAC 51-42-1109   Refrigerant piping, containers and valves.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1110   Erection of refrigerant piping.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1111   Refrigerant control valves.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1112   Pressure-limiting devices.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1113   Pressure-relief devices.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1114   Pressure-relief device settings.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1115   Marking of pressure-relief devices.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1116   Over-pressure protection.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1117   Discharge piping.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1118   Special discharge requirements.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1119   Ammonia discharge.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1120   Detection and alarm systems.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1121   Equipment identification.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1122   Testing of refrigeration equipment.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1123   Maintenance and operation.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1124   Storage of refrigerants and refrigerant oils.   This section is not adopted.

[]


NEW SECTION
WAC 51-42-1126   Tables not adopted.  


Table 11-A - Refrigerant groups, properties and allowable quantities. This table is not adopted.


Table 11-B - Permissible refrigeration systems and refrigerants. This table is not adopted.


Table 11-C - Value of f (f) for equation 11-7. This table is not adopted.


Table 11-D - Field leak test pressures in psig. This table is not adopted.


Table 11-E - Condensate waste size. This table is not adopted.

[]


NEW SECTION
WAC 51-42-1301   Section 1301 -- General.  


1301.2 Other authorities. In addition to the Uniform Mechanical Code, provisions of chapter 480-93 WAC regarding gas pipeline safety may also apply to single meter installations serving more than one building. The provisions of chapter 480-93 WAC are enforced by the Washington Utilities and Transportation Commission.

[]

Washington State Code Reviser's Office